Heat Controller A-13 installation instructions Ix. Wiring, E.Condensate Drain, A. Power Supply

Models: A-13

1 56
Download 56 pages 46.58 Kb
Page 16
Image 16
E.CONDENSATE DRAIN

TABLE 3

METER TIME IN MINUTES AND SECONDS FOR NORMAL

INPUT RATING OF FURNACES EQUIPPED FOR NATURAL

OR LP GAS

INPUT

METER

 

HEATING VALUE OF GAS BTU PER CU. FT.

 

SIZE

900

1000

1040

1100

2500

BTU/HR

 

CU. FT.

MIN.

SEC.

MIN.

SEC.

MIN.

SEC.

MIN.

SEC.

MIN.

SEC.

40,000

ONE

1

21

1

30

1

34

1

39

3

45

TEN

13

30

15

0

15

36

16

30

37

30

 

60,000

ONE

0

54

1

0

1

3

1

6

2

30

TEN

9

0

10

0

10

24

11

0

25

0

 

80,000

ONE

0

41

0

45

0

47

0

50

1

53

TEN

6

45

7

30

7

48

8

15

18

45

 

100,000

ONE

0

33

0

36

0

38

0

40

1

30

TEN

5

24

6

0

6

15

6

36

15

0

 

FIGURE 16

CONDENSATE DRAIN

DO NOT OVERTIGHTEN DRAIN FITTING

NOTICE: DERATING OF THE HEATING INPUT FOR HIGH ALTITUDE IN THE FIELD IS UNLAWFUL IN CANADA (REFER TO CAN/CGA 2.17). UNITS INSTALLED IN ALTITUDES GREATER THAN 2,000 FEET (610 METERS) MUST BE SHIPPED FROM THE FACTORY OR FROM A FACTORY AUTHORIZED CONVERSION STATION WITH THE HEATING INPUT DERATED BY 10% SO AS TO OPERATE PROPERLY IN ALTITUDES FROM 2,000 - 4,500 FEET (610 - 1,373 METERS).

E.CONDENSATE DRAIN

The condensate drain connection of the evaporator is threaded 3/4nominal P.V.C. pipe. IMPORTANT: Install a condensate trap to ensure proper condensate drainage. See Figure 16.

IX. WIRING

A. POWER SUPPLY

!WARNING

TURN OFF THE MAIN ELECTRICAL POWER AT THE BRANCH CIRCUIT DIS- CONNECT CLOSEST TO THE UNIT BEFORE ATTEMPTING ANY WIRING. FAIL- URE TO DO SO CAN CAUSE ELECTRICAL SHOCK RESULTING IN PERSONAL INJURY OR DEATH.

1.All wiring should be made in accordance with the National Electrical Code.

Consult the local power company to determine the availability of sufficient power to operate the unit. Check the voltage at power supply to make sure it corresponds to the unit’s RATED VOLTAGE REQUIREMENT. Install a branch circuit disconnect near the rooftop, in accordance with the N.E.C., C.E.C. or local codes. A bracket is provided with the unit for mounting of the disconnect. See Figure 17.

2.It is important that proper electrical power is available at the unit. Voltage should not vary more than 10% from that stamped on the unit nameplate. On three phase units, phases must be balanced within 3%.

3.For branch circuit wiring (main power supply to unit disconnect), the minimum wire size for the length of run can be determined from Table 3 using the circuit ampacity found on the unit rating plate. Use the smallest wire size allowable in Table 4 from the unit dis- connect to unit.

NOTE: A bracket is provided with the unit for mounting the branch circuit disconnect to the unit. This is the recommended location for the disconnect. See Figure 17.

4.For through the base wiring entry reference Figure 18. All fittings and conduit are field supplied for this application. Reference the chart with Figure 18 for proper hole and conduit size.

16

Page 16
Image 16
Heat Controller A-13 installation instructions Ix. Wiring, E.Condensate Drain, A. Power Supply