Heat Controller A-13 Xii. General Data - Tgc Models, NOMINAL SIZES 3-5 TONS 10.6-17.6 kW

Models: A-13

1 56
Download 56 pages 46.58 Kb
Page 27
Image 27
XII. GENERAL DATA - TGC MODELS

XII. GENERAL DATA - TGC MODELS

NOMINAL SIZES 3-5 TONS [10.6-17.6 kW]

Model TGC-Series

036A3K-080

036A-3K-120

036A-1K-080

036A-1K-120

Cooling Performance1

 

 

 

Continued ->

Gross Cooling Capacity Btu [kW]

36,800 [10.78]

36,800 [10.78]

36,800 [10.78]

36,800 [10.78]

EER/SEER2

11.4/13

11.4/13

11.4/13

11.4/13

Nominal CFM/ARI Rated CFM [L/s]

1200/1200 [566/566]

1200/1200 [566/566]

1200/1200 [566/566]

1200/1200 [566/566]

ARI Net Cooling Capacity Btu [kW]

35,400 [10.37]

35,400 [10.37]

35,400 [10.37]

35,400 [10.37]

Net Sensible Capacity Btu [kW]

26,200 [7.68]

26,200 [7.68]

26,200 [7.68]

26,200 [7.68]

Net Latent Capacity Btu [kW]

9,200 [2.7]

9,200 [2.7]

9,200 [2.7]

9,200 [2.7]

Net System Power kW

3.1

3.1

3.1

3.1

 

 

 

 

 

Heating Performance (Gas)3

 

 

 

 

Heating Input Btu [kW]

80,000 [23.44]

120,000 [35.16]

80,000 [23.44]

120,000 [35.16]

Heating Output Btu [kW]

64,800 [18.99]

97,200 [28.48]

62,500 [18.31]

94,500 [27.69]

Temperature Rise Range °F [°C]

30-60 [16.7/33.3]

50-80 [27.8/44.4]

30-60 [16.7/33.3]

50-80 [27.8/44.4]

AFUE %

80

80

80

80

Steady State Efficiency (%)

81

81

81

81

No. Burners

4

6

4

6

No. Stages

1

1

1

1

Gas Connection Pipe Size in. [mm]

0.5 [12.7]

0.5 [12.7]

0.5 [12.7]

0.5 [12.7]

 

 

 

 

 

Compressor

 

 

 

 

No./Type

1/Scroll

1/Scroll

1/Copeland Scroll

1/Copeland Scroll

 

 

 

 

 

Outdoor Sound Rating (dB)4

78

78

78

78

 

 

 

 

 

Outdoor Coil - Fin Type

Louvered

Louvered

Louvered

Louvered

Tube Type

Rifled

Rifled

Rifled

Rifled

Tube Size in. [mm] OD

0.375 [9.5]

0.375 [9.5]

0.375 [9.5]

0.375 [9.5]

Face Area sq. ft. [sq. m]

16.91 [1.57]

16.91 [1.57]

16.91 [1.57]

16.91 [1.57]

Rows / FPI [FPcm]

1 / 22 [9]

1 / 22 [9]

1 / 22 [9]

1 / 22 [9]

 

 

 

 

 

Indoor Coil - Fin Type

Corrugated

Corrugated

Corrugated

Corrugated

Tube Type

Rifled

Rifled

Rifled

Rifled

Tube Size in. [mm]

0.375 [9.5]

0.375 [9.5]

0.375 [9.5]

0.375 [9.5]

Face Area sq. ft. [sq. m]

5.17 [0.48]

5.17 [0.48]

5.17 [0.48]

5.17 [0.48]

Rows / FPI [FPcm]

2 / 17 [7]

2 / 17 [7]

2 / 17 [7]

2 / 17 [7]

Refrigerant Control

TX Valves

TX Valves

TX Valves

TX Valves

Drain Connection No./Size in. [mm]

1/0.75 [19.05]

1/0.75 [19.05]

1/0.75 [19.05]

1/0.75 [19.05]

 

 

 

 

 

Outdoor Fan - Type

Propeller

Propeller

Propeller

Propeller

No. Used/Diameter in. [mm]

1/24 [609.6]

1/24 [609.6]

1/24 [609.6]

1/24 [609.6]

Drive Type/No. Speeds

Direct/1

Direct/1

Direct/1

Direct/1

CFM [L/s]

3680 [1737]

3680 [1737]

3680 [1737]

3680 [1737]

No. Motors/HP

1 at 1/3 HP

1 at 1/3 HP

1 at 1/3 HP

1 at 1/3 HP

Motor RPM

1075

1075

1075

1075

 

 

 

 

 

Indoor Fan - Type

FC Centrifugal

FC Centrifugal

FC Centrifugal

FC Centrifugal

No. Used/Diameter in. [mm]

1/10x10 [254x254]

1/10x10 [254x254]

1/10x10 [254x254]

1/10x10 [254x254]

Drive Type/No. Speeds

Direct/3

Direct/3

Direct/3

Direct/3

No. Motors

1

1

1

1

Motor HP

1/2

1/2

1/2

1/2

Motor RPM

1075

1075

1075

1075

Motor Frame Size

48

48

48

48

 

 

 

 

 

Filter - Type

Disposable

Disposable

Disposable

Disposable

Furnished

Yes

Yes

Yes

Yes

(NO.) Size Recommended in. [mm x mm x mm]

(1)1x16x25 [25x406x635]

(1)1x16x25 [25x406x635]

(1)1x16x25 [25x406x635]

(1)1x16x25 [25x406x635]

 

(1)1x16x25 [25x406x635]

(1)1x16x25 [25x406x635]

(1)1x16x25 [25x406x635]

(1)1x16x25 [25x406x635]

 

 

 

 

 

Refrigerant Charge Oz. [g]

96 [2722]

96 [2722]

96 [2722]

96 [2722]

 

 

 

 

 

Weights

 

 

 

 

Net Weight lbs. [kg]

543 [246]

543 [246]

543 [246]

543 [246]

Ship Weight lbs. [kg]

550 [249]

550 [249]

550 [249]

550 [249]

 

 

 

 

 

NOTES:

1.Cooling Performance is rated at 95° F ambient, 80° F entering dry bulb, 67° F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Units are certified in accordance with the Unitary Air Conditioner Equipment certification program, which is based on ARI Standard 210/240 or 360.

2.EER and/or SEER are rated at ARI conditions and in accordance with DOE test procedures.

3.Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standard Institute standards. Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level.

4.Outdoor Sound Rating shown is tested in accordance with ARI Standard 270.

27

Page 27
Image 27
Heat Controller A-13 Xii. General Data - Tgc Models, NOMINAL SIZES 3-5 TONS 10.6-17.6 kW, Continued