Additional gas charging

Troubleshooting Guide

Additional gas charging

(Gas leakage)

When refrigerant is insufficient by leakage, recharge the unit with the refrigerant up to normal oper- ating suction pressure.

Use the graph or the equation below to get operating suction pressure according to indoor and out- door temperature.

Suction pressure was measured at 3-way valve service port after operating the unit for 10 minutes.

The method of using graph

-Find outdoor temperature.

-Find indoor temperature onto the curve of outdoor temperature.

-Read suction pressure at the axis of ordinates.

The method of using equation

-. Calculate suction pressure after putting indoor and outdoor temperature into the equation.

Operating Suction Pressure (For R410A)

(According to Indoor & Outdoor Temperature)

Suction Pressure

(PSI)

 

(At operating the Unit for 10 minutes)

184.9

 

170.7

122˚F

 

156.5

104˚F

142.2

86˚F

128

68˚F

113.8

50˚F

0˚F

 

99.5

85

71.1

41

50

59

68

77

86

95

104

Indoor Temp. (˚F)

Outdoor Temp. (˚F)

Service Manual 49