Operation
Operation
FunctionofControls
• DISPLAY
1) C/O Model
Operation Indicator
•ON while in appliance operation, OFF while in appliance pause.
•Flashing while in disconnection or short in Thermistor. (3 sec off / 0.5 sec on)
Timer Indicator
• ON while in timer mode (on/off), OFF when timer mode is completed or canceled.
Comp. Running Incidator
•While in appliance operation, ON while in outdoor unit compressor running, OFF while in compres- sor off.
2)H/P Model
Operation Indicator
•ON while in appliance operation, OFF while in appliance pause.
•Flashing while in disconnection or short in Thermistor. (3 sec off / 0.5 sec on)
Timer Indicator
• ON while in timer mode (on/off), OFF when timer mode is completed or canceled.
Defrost Indicator
•OFF except when hot start during heating mode operation or while in defrost control.
■Cooling Mode Operation
•When the intake air temperature reaches 0.5°C(0.9°F) below the setting temp, the compressor and the outdoor fan stop.
•When it reaches 0.5°C(0.9°F) above the setting temp, they start to operate again.
Compressor ON Temp | ➲ Setting Temp+0.5°C(0.9°F) |
Compressor OFF Temp | ➲ Setting |
•While in compressor running, operating with the airflow speed set by the remote control. While in compressor not running, operating with the low airflow speed regardless of the setting.
■Healthy Dehumidification Mode
•When the dehumidification operation input by the remote control is received, the intake air tempera- ture is detected and the setting temp is automatically set according to the intake air temperature.
26°C(78.8°F) ≤ Intake Air Temp➲ 25°C(77°F)
24°C(75.2°F) ≤ Intake Air Temp<26°C(78.8°F) ➲ Intake Air
18°C(64.4°F) ≤ Intake Air Temp<24°C(75.2°F) | ➲ | Intake Air |
Intake Air Temp<18°C(64.4°F) | ➲ | 18°C(64.4°F) |