Heat Controller, Inc.

 

 

 

HBH/V SERIES

 

Engineering Design Guide

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Electrical Data

 

 

 

 

 

 

 

 

 

 

High Static Blower

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HB

Voltage

Rated

Voltage

Compressor

Fan

Total

Min

Max

 

 

Min/

 

 

 

Motor

Unit

Circuit

Fuse/

 

 

Model

Code

Voltage

QTY

RLA

LRA

 

 

Max

FLA

FLA

Amp

HACR

 

 

 

 

 

 

 

015

1

208-230/60/1

197/254

1

6.0

29.0

1.00

7.0

8.5

15

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8

265/60/1

239/292

1

5.4

28.0

0.86

6.3

7.6

15

 

 

 

 

 

018

1

208-230/60/1

197/254

1

7.2

33.0

1.50

8.7

10.5

15

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8

265/60/1

239/292

1

5.9

28.0

1.30

7.2

8.7

15

 

 

 

 

 

024

1

208-230/60/1

197/254

1

12.8

58.3

3.00

15.8

19.0

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8

265/60/1

239/292

1

9.6

54.0

2.70

12.3

14.7

20

 

 

 

 

 

 

1

208-230/60/1

197/254

1

14.1

73.0

3.00

17.1

20.6

30

 

 

030

8

265/60/1

239/292

1

11.2

60.0

2.70

13.9

16.7

25

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

208-230/60/3

197/254

1

8.9

58.0

3.00

11.9

14.1

20

 

 

 

 

 

 

4

460/60/3

414/506

1

4.2

28.0

1.70

5.9

7.0

15

 

 

 

1

208-230/60/1

197/254

1

16.7

79.0

3.00

19.7

23.9

40

 

 

036

8

265/60/1

239/292

1

13.5

72.0

2.70

16.2

19.6

30

 

 

3

208-230/60/3

197/254

1

10.4

73.0

3.00

13.4

16.0

25

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

460/60/3

414/506

1

5.8

38.0

1.70

7.5

9.0

15

 

 

 

1

208-230/60/1

197/254

1

17.9

112.0

3.00

20.9

25.4

40

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

042

3

208-230/60/3

197/254

1

13.5

88.0

3.00

16.5

19.9

30

 

 

4

460/60/3

414/506

1

6.0

44.0

1.70

7.7

9.2

15

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

575/60/3

518/633

1

4.9

34.0

1.40

6.3

7.5

15

 

 

 

1

208-230/60/1

197/254

1

21.8

117.0

4.90

26.7

32.2

50

 

 

048

3

208-230/60/3

197/254

1

13.7

83.1

4.90

18.6

22.0

35

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

460/60/3

414/506

1

6.2

41.0

2.50

8.7

10.3

15

 

 

 

 

 

 

5

575/60/3

518/633

1

4.8

33.0

1.90

6.7

7.9

15

 

 

 

1

208-230/60/1

197/254

1

26.3

134.0

5.80

32.1

38.7

60

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

060

3

208-230/60/3

197/254

1

15.6

110.0

5.80

21.4

25.3

40

 

 

4

460/60/3

414/506

1

7.8

52.0

2.60

10.4

12.4

20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

575/60/3

518/633

1

5.8

38.9

2.30

8.1

9.6

15

 

HACR circuit breaker in USA only

All fuses Class RK-5

30

Page 31
Image 31
Heat Controller HBH/V manual Electrical Data High Static Blower