Heat Controller HBH/V Air Flow Correction Table, Engineering Design Guide, Hbh/V Series, Airflow

Models: HBH/V

1 35
Download 35 pages 35.8 Kb
Page 20
Image 20
Air Flow Correction Table

Engineering Design Guide

HBH/V SERIES

Heat Controller, Inc.

 

 

 

Air Flow Correction Table

 

 

 

 

 

 

Cooling Corrections

 

 

 

 

 

 

Ent Air

Total Clg

 

 

 

Sens Clg Cap Multipliers - Entering DBº F

 

 

 

Power

Heat of Rej

WBº F

Cap

 

 

 

 

 

 

 

 

 

 

 

65

 

70

75

80

80.6

 

85

90

95

 

 

 

 

 

 

 

 

 

 

50

0.7800

0.9778

 

*

*

*

*

 

*

*

*

0.9972

0.8243

 

 

 

 

 

 

 

 

 

 

 

 

 

 

55

0.8327

0.8966

 

1.0556

*

*

*

 

*

*

*

0.9980

0.8667

 

 

 

 

 

 

 

 

 

 

 

 

 

 

60

0.8954

0.7505

 

0.9184

1.1056

*

*

 

*

*

*

0.9988

0.9169

 

 

 

 

 

 

 

 

 

 

 

 

 

 

65

0.9681

 

 

0.6778

0.8992

1.1213

1.1480

 

1.3439

*

*

0.9996

0.9747

 

 

 

 

 

 

 

 

 

 

 

 

 

 

66.2

0.9871

 

 

0.6103

0.8420

1.0698

1.0969

 

1.2938

*

*

0.9999

0.9897

 

 

 

 

 

 

 

 

 

 

 

 

 

 

67

1.0000

 

 

0.5507

0.7782

1.0000

1.0262

 

1.2161

1.4266

*

1.0000

1.0000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

70

1.0508

 

 

 

0.6408

0.8856

0.9135

 

1.1082

1.3087

1.4869

1.0005

1.0403

 

 

 

 

 

 

 

 

 

 

 

 

 

 

75

1.1435

 

 

 

 

0.6085

0.6403

 

0.8566

1.0663

1.2376

1.0014

1.1135

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

* Sensible capacity equals total capacity.

 

 

 

 

 

 

 

 

 

 

 

ARI/ISO/ASHRAE 13256-1 uses entering air conditions of Cooling - 80.6°F DB/ 66.2°F WB, and Heating - 68°F DB/ 59°F WB entering air temperature.

 

Heating Corrections

Ent Air

Htg Cap

Power

Heat of

DBº F

Ext

 

 

 

 

 

 

45

1.0507

0.7802

1.1314

 

 

 

 

50

1.0327

0.8227

1.0953

 

 

 

 

55

1.0195

0.8683

1.0646

 

 

 

 

60

1.0102

0.9168

1.0380

 

 

 

 

65

1.0033

0.9680

1.0139

 

 

 

 

68

1.0000

1.0000

1.0000

 

 

 

 

70

0.9979

1.0218

0.9908

 

 

 

 

75

0.9928

1.0781

0.9673

 

 

 

 

80

0.9866

1.1367

0.9419

 

 

 

 

Air Flow Correction Table

Airflow

 

 

Cooling

 

 

 

Heating

 

% of

Total

Sensible

Sens/Tot

Power

Heat of

Heating

Power

Heat of

Rated

Capacity

Capacity

Ratio

Rejection

Capacity

Extraction

 

 

75

0.9764

1.1134

0.9368

0.9605

0.8837

0.9200

0.9606

0.9605

 

 

 

 

 

 

 

 

 

81.25

0.9829

1.0789

0.9551

0.9730

0.9130

0.9384

0.9691

0.9722

 

 

 

 

 

 

 

 

 

87.5

0.9889

1.0484

0.9717

0.9837

0.9393

0.9548

0.9784

0.9826

 

 

 

 

 

 

 

 

 

93.75

0.9947

1.0222

0.9867

0.9927

0.9668

0.9739

0.9887

0.9919

 

 

 

 

 

 

 

 

 

100

1.0000

1.0000

1.0000

1.0000

1.0000

1.0000

1.0000

1.0000

 

 

 

 

 

 

 

 

 

106.25

1.0050

0.9820

1.0116

1.0055

1.0434

1.0377

1.0122

1.0069

 

 

 

 

 

 

 

 

 

112.5

1.0096

0.9681

1.0216

1.0093

1.1016

1.0915

1.0253

1.0126

 

 

 

 

 

 

 

 

 

118.75

1.0138

0.9583

1.0299

1.0113

1.1790

1.1658

1.0394

1.0171

 

 

 

 

 

 

 

 

 

125

1.0177

0.9527

1.0365

1.0116

1.2798

1.2652

1.0544

1.0204

 

 

 

 

 

 

 

 

 

19