Heat Controller, Inc.

HBH/V SERIES

Engineering Design Guide

 

 

 

Selection Procedure

Step 1 Determine the actual heating and cooling loads at the desired dry bulb and wet bulb conditions.

Step 2 Obtain the following design parameters: Entering water temperature, water flow rate in GPM, air flow in CFM, water flow pressure drop and design wet and dry bulb temperatures. Air flow CFM should be between 300 and 450 CFM per ton. Unit water pressure drop should be kept as close as possible to each other to make water balancing easier. Go to the appropriate tables and find the proper indicated water flow and water temperature.

Step 3 Select a unit based on total and sensible cooling conditions. Select a unit which is closest to, but no larger than, the actual cooling load.

Step 4 Enter tables at the design water flow and water temperature. Read the total and sensible cooling capacities (Note: interpolation is permissible, extrapolation is not).

Step 5 Read the heating capacity. If it exceeds the design criteria it is acceptable. It is quite normal for Water- Source Heat Pumps to be selected on cooling capacity only since the heating output is usually greater than the cooling capacity.

Step 6 Determine the correction factors associated with the variable factors of dry bulb, wet bulb and air flow.

Corrected Total Cooling =

tabulated total cooling x wet bulb correction x air flow correction

Corrected Sensible Cooling =

tabulated sensible cooling x dry bulb correction x air flow correction

Step 7 Compare the corrected capacities to the load requirements. Normally if the capacities are within 10% of the loads, the equipment is acceptable. It is better to undersize than oversize, as undersizing improves humidity control, reduces sound levels and extends the life of the equipment.

Step 8 When completed, calculate water temperature rise and assess the selection. If the units selected are not within 10% of the load calculations, then review what effect changing the GPM, water temperature and/or air flow and air temperature would have on the corrected capacities. If the desired capacity cannot be achieved, select the next larger or smaller unit and repeat the procedure. Remember, when in doubt, undersize slightly for best performance.

Example Equipment Selection For Cooling

Step 1 Load Determination:

Assume we have determined that the appropriate cooling load at the desired dry bulb 80°F and wet bulb 65°F conditions is as follows:

Total Cooling

23,700 BTUH

Sensible Cooling

16,500 BTUH

Entering Air Temp.... 80°F Dry Bulb / 65°F Wet Bulb

Step 2 Design Conditions:

Similarly, we have also obtained the following design parameters:

Entering Water Temp

90°F

Water Flow (Based upon 10°F rise in temp.) .6.0 GPM

Air Flow

800 CFM

Step 3, 4 & 5 HP Selection:

After making our preliminary selection (TC024), we enter the tables at design water flow and water temperature and read Total Cooling, Sens. Cooling and Heat of Rej. capacities:

Total Cooling

23,400 BTUH

Sensible Cooling

17,500 BTUH

Heat of Rejection

30,200 BTUH

Step 6 & 7 Entering Air and Airflow Corrections:

Next, we determine our correction factors.

Table

Ent Air Air Flow Corrected

 

Corrected Total Cooling = 23,400

x 0.9681 x 1.0050 = 22,767

Corrected Sens Cooling = 17,500

x 1.1213 x 0.9820 = 19,270

Corrected Heat of Reject = 30,200 x 0.9747 x 1.0434 = 30,713

Step 8 Water Temperature Rise Calculation & Assessment:

Actual Temperature Rise

10.2°F

When we compare the Corrected Total Cooling and Corrected Sensible Cooling figures with our load requirements stated in Step 1, we discover that our selection is within +/- 10% of our sensible load requirement. Furthermore, we see that our Corrected Total Cooling figure is within 1,000 Btuh the actual indicated load.

4

Page 5
Image 5
Heat Controller HBH/V manual Example Equipment Selection For Cooling