Installation and Operations Manual

Table 17. Henry Relief Valve Capacity Rating

Type

Catalog

Size Connection

 

Standard Pressure Settings PSIG

 

Number

Inlet

Outlet

350

 

400

425

 

450

 

 

 

Angle

526E

3/8 MPT

3/8 FLARE

10.2

 

11.6

12.3

 

13.0

 

 

 

 

 

 

 

 

 

527E

1/2 MPT

5/8 FLARE

28.5

 

32.4

34.4

 

36.3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5231

3/8 MPT

3/8 FLARE

11.2

 

12.7

13.5

 

14.3

 

5231-A

3/8 MPT

1/2 FLARE

18.6

 

21.1

22.4

 

23.7

 

 

 

 

 

 

 

 

 

 

 

5231

1/2 MPT

5/8 FLARE

18.6

 

21.1

22.4

 

23.7

 

 

 

 

 

 

 

 

 

 

Straight

5232

1/2 MPT

5/8 FLARE

28.1

 

32.0

33.9

 

35.8

Through

5240-1/2

1/2 MPT

3/4 FPT

41.2

 

46.8

49.1

 

52.5

 

 

 

 

 

 

 

 

 

 

 

5242-3/4

3/4 MPT

3/4 FPT

41.2

 

46.8

49.1

 

52.5

 

 

 

 

 

 

 

 

 

 

 

5244-1

1 MPT

1 FPT

74.0

 

84.2

89.3

 

94.4

 

5246-1-1/4

1-1/4 MPT

1-1/4 FPT

129.7

 

147.5

156.4

 

165.4

 

 

 

 

 

 

 

 

 

 

Table 18. Discharge Piping Table

Maximum Length of Discharge Pipe in Feet

* For 400 PSIG Pressure Setting

Relief Device

Soft Copper Tube (OD)

 

 

Schedule 40 Pipe

 

 

Capacity

 

 

 

 

 

 

 

 

 

3/8”

1/2”

5/8”

1/2”

3/4”

1”

1-1/4”

1-1/2”

2”

Lbs. Air/Min.

 

 

 

 

 

 

 

 

 

10

3-1/2

19-1/4

61

108

445

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12

2-1/2

12-1/4

44

75

308

 

 

 

 

 

 

 

 

 

 

 

 

 

 

14

2

9-1/2

32

56

228

 

 

 

 

18

 

5-1/4

19-1/4

33

137

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20

 

4-1/4

16

28

110

371

 

 

 

 

 

 

 

 

 

 

 

 

 

25

 

2-1/2

9-1/2

18

72

238

 

 

 

30

 

2

7

12

49

165

 

 

 

 

 

 

 

 

 

 

 

 

 

35

 

2

5-1/4

9

37

121

 

 

 

 

 

 

 

 

 

 

 

 

 

40

 

 

3-1/2

7

28

93

366

 

 

50

 

 

2-1/2

4

18

60

233

 

 

 

 

 

 

 

 

 

 

 

 

70

 

 

 

3

9

30

119

257

 

 

 

 

 

 

 

 

 

 

 

80

 

 

 

2

7

23

91

198

 

90

 

 

 

2

5

18

72

156

 

 

 

 

 

 

 

 

 

 

 

125

 

 

 

 

3

10

37

81

282

 

 

 

 

 

 

 

 

 

 

150

 

 

 

 

2

7

26

56

196

For Relief Devices set at 400 psig

Obtain the capacity at 400 psig setting

Locate this capacity or the nearest larger capacity in the left-hand column of the discharge piping table above and read across to obtain the maximum lengths for each tube and pipe size

For relief devices set at 350 psig, use the above table and multiply by .75 to determine maximum lengths For relief devices set at 425 psig, use the above table and multiply by 1.15 to determine maximum lengths For relief devices set at 450 psig, use the above table and multiply by 1.25 to determine maximum lengths

24

Part # 25000102

Page 24
Image 24
Heatcraft Refrigeration Products 25000102 operation manual Henry Relief Valve Capacity Rating, Discharge Piping Table