Installation and Operations Manual

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 14. Oil Safety Switch

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Carlyle

Danfoss

 

Time

 

 

 

Pressure

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Diff. Psi (bar)

 

Reset

 

 

 

 

 

 

Part No.

Part No.

 

Delay

 

 

 

 

 

 

 

 

 

 

 

 

Cut-In

 

Cut-Out

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

634-2008

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OR

60B2101

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P529-2130

 

 

 

45 sec.

 

 

8 – 11

4 - 8

 

 

Manual

 

 

 

 

 

 

634-2050

 

 

 

 

(.55 - .76)

 

(.28 - .55)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OR

60B2151

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P529-2100

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Carlyle

Johnson

 

Time

 

 

 

Pressure

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Diff. Psi (bar)

 

Reset

 

 

 

 

 

 

Part No.

Part No.

 

Delay

 

 

 

 

 

 

 

 

 

 

 

 

Cut-In

 

Cut-Out

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

O6DA660115

P345

 

45 sec.

 

 

8 – 11

4 - 8

 

 

Manual

 

 

 

 

 

 

 

 

(.55 - .76)

 

(.28 - .55)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 15. Part Load Performance Multipliers

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Multiplication Factor

 

Multiplication Factor

 

 

Compressor Model

 

 

For 1 Bank Unloaded

 

For 2 Bank Unloaded

 

 

 

 

Capacity

 

Power

 

EER

 

Capacity

 

Power

 

 

EER

 

 

All 4 Cylinder Models

 

.49

 

.57

 

 

.86

 

 

-

 

-

 

 

 

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

All 6 Cylinder Models

 

.67

 

.73

 

 

.92

 

 

.32

 

.46

 

 

 

.70

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 16. Required Differential Pressure for Unloader Operation

 

 

 

 

 

 

 

 

 

 

Suction Pressure

 

 

P Required-Discharge Minus

 

Application

 

 

 

 

Suction Pressure Psi (bar)

 

 

 

Range Psi (bar)

 

 

 

 

 

 

 

 

 

 

 

 

 

O6D

 

 

 

 

 

 

O6E

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L.T. R-502, 404A, 507

 

10-25

 

(1.7-2.7)

 

30

 

(2.1)

 

 

30

 

(2.1)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

M.T. R-502, 404A, 507

 

30-60

 

(3.1-5.2)

 

40

 

(2.8)

 

 

45

 

(3.1)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L.T. R-12, 134A

 

10-30

 

(1.7-3.1)

 

30

 

(2.1)

 

 

35

 

(2.4)

 

M.T. R-22 or H.T. R-22

 

30-90

 

(3.1-7.2)

 

50

 

(3.5)

 

 

55

 

(3.8)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Multiply compressor rating data by above factors when used with blocked suction unloading

3-Phase Voltage Monitor

The microprocessor-based voltage and phase sensing circuit constantly monitors the three phase voltages to detect harmful power line conditions.When a harmful condition is detected, the phase monitor output relay is deactivated after a specified trip delay. The output relay reactivates after power line conditions return to an acceptable level for a specified amount of time (Restart Delay). The trip delay prevents nuisance tripping due to rapidly fluctuating power line conditions.

The Bicolor LED indicator light is green in normal conditions and red during trip conditions. On initial start-up, if the light is continuously red, the unit electrical phase may need to be reversed. Each main power line should be checked for proper voltage and imbalance prior to reversing a phase. Also check the settings of the Voltage Monitor for proper field condition.

For semi-hermetic compressor units, two of the three power monitor leads on the Voltage Monitor to L1, L2, and L3 may need to be switched. For units with Scroll® or Screw compressors, which are rotation sensitive, two of the main power lines to the compressor unit will have to be switched to match the correct rotation of the compressors. The rotation of Screw and Scroll® compressors has been properly phased in the manufacturing plant prior to shipping.

22

Part # 25000102

Page 22
Image 22
Heatcraft Refrigeration Products 25000102 operation manual Part Load Performance Multipliers, Phase Voltage Monitor