Installation and Operations Manual

Table 2. Pressure Loss of Liquid Refrigerants

(In Liquid Line Risers - Expressed in Pressure Drop, PSIG, and Subcooling Loss, °F)

Liquid Line Rise in Feet

Refrigerant

10’

 

15’

 

20’

 

25’

 

30’

 

40’

50’

75’

100’

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PSIG

 

°F

PSIG

 

°F

PSIG

 

°F

PSIG

 

°F

PSIG

 

°F

PSIG

°F

PSIG

°F

PSIG

°F

PSIG

°F

 

 

 

 

 

 

R-12

5.4

 

2.8

8.1

 

4.2

10.7

 

5.4

13.4

 

6.9

16.1

 

8.3

21.5

11.3

26.9

14.3

40.3

22.4

53.7

31.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

R-22

4.8

 

1.6

7.3

 

2.3

9.7

 

3.1

12.1

 

3.8

14.5

 

4.7

19.4

6.2

24.2

8.0

36.3

12.1

48.4

16.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

R-502

4.9

 

1.5

7.3

 

2.2

9.7

 

3.0

12.1

 

3.7

14.6

 

4.5

19.5

6.0

24.3

7.6

36.4

11.5

48.6

14.8

R-134A

4.9

 

2.0

7.4

 

2.9

9.8

 

4.1

12.3

 

5.2

14.7

 

6.3

19.7

8.8

24.6

11.0

36.8

17.0

49.1

23.7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

R-404A/R-507

4.1

 

1.1

6.1

 

1.6

8.2

 

2.1

10.2

 

2.7

12.2

 

3.3

16.3

4.1

20.4

5.6

30.6

8.3

40.8

11.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Based on 110°F liquid temperature at bottom of riser

Table 3. Equivalent Feet of Pipe

(Due to Value and Fitting Friction)

Copper Tube

1/2

5/8

7/8

1-1/8

1-3/8

1-5/8

2-1/8

2-5/8

3-1/8

3-5/8

4-1/8

5-1/8

6-1/8

OD, Type “L”

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Globe Value (Open)

14

16

22

28

36

42

57

69

83

99

118

138

168

Angle Value (Open)

7

9

12

15

18

21

28

34

42

49

57

70

83

 

 

 

 

 

 

 

 

 

 

 

 

 

 

90° Turn Through Tee

3

4

5

6

8

9

12

14

17

20

22

28

34

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Tee - Straight Through

.75

1

1.5

2

2.5

3

3.5

4

5

6

7

9

11

or Sweep Below

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

90° Elbow or Reducing

1

2

2

3

4

4

5

7

8

10

12

14

16

Tee (Straight Through)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

Part # 25000102

Page 10
Image 10