Parallel Compressor Systems

Symptom

 

Cause

 

Remedy

 

 

 

 

 

Low

1.

Insufficient refrigerant in system

1.

Check for leaks. Repair and add charge

Discharge

2.

Faulty condenser temp. regulation

2.

Check condenser control operation

Pressure

3.

Compressor suction or discharge valve inefficiencies

3.

Clean or replace leaky valve plates

 

4.

Low suction pressure

4.

See corrective steps for low suction pressure

 

5.

Head pressure control valve set wrong

5.

Adjust valve or install a head pressure control valve

 

 

or no head pressure control valve

 

 

 

 

 

 

 

High Suction

1.

Excessive load

1.

Reduce load or add additional equipment

Pressure

2.

Expansion valve overfeeding

2.

Check remote bulb. Regulate superheat

 

 

 

 

 

Low Suction

1.

Lack of refrigerant

1.

Check for leaks. Repair and add charge

Pressure

2.

Evaporator dirty or iced

2.

Defrost or clean coil

 

3.

Clogged liquid line filter drier

3.

Replace cartridge(s)

 

4.

Clogged suction line or compressor

4.

Clean strainer or replace filters

 

 

suction strainer

 

 

 

5.

Expansion valve malfunctioning

5.

Check and reset for proper superheat

 

6.

Condensing temperature too low

6.

Check means for regulating

 

 

 

 

condensing temperature

 

7.

Improper TXV

7.

Check for proper sizing

 

 

 

 

 

Little or No

1.

Clogged suction oil strainer

1.

Clean

Oil Pressure

2.

Excessive liquid in crankcase

2.

Check crankcase heater. Reset TXV for

 

 

 

 

higher superheat. Check liquid line solenoid

 

 

 

 

valve for proper operation.

 

3.

Low oil pressure safety switch defective

3.

Replace

 

4.

Worn oil pump

4.

Replace

 

5.

Oil pump reversing gear stuck in

5.

Reverse direction of compressor rotation

 

 

the wrong position

 

 

 

6.

Low oil level

6.

Determine where the oil is or add oil

 

7.

Worn bearings

7.

Replace compressor

 

8.

Loose fitting on oil lines

8.

Check and tighten fittings

 

9.

Pump house gasket leaks

9.

Replace gasket

 

 

 

 

 

Compressor

1.

Lack of refrigerant

1.

Check for leaks. Repair and add charge

Loses Oil

2.

Excessive compression ring blowby

2.

Replace compressor

 

3.

Refrigerant floods back

3.

Maintain proper superheat at compressor

 

4.

Improper piping or traps

4.

Correct piping

 

 

 

 

 

Compressor

1.

Operating beyond design limits

1.

Add facilities so that conditions are within

Thermal

 

 

 

allowable limits

Protector

2.

Discharge valve partially shut

2.

Open valve

Switch Open

3.

Blown valve plate gasket

3.

Replace gasket

 

4.

Dirty condenser coil

4.

Clean coil

 

5.

Overcharged system

5.

Reduce charge

 

 

 

 

 

Parallel Compressor Systems Installation & Operations Manual, October 2004

35

Page 35