Error Codes
The L2002 series inverters will trip on
Basic Error Codes
Error | Name | Probable Cause(s) | |
Code | |||
|
| ||
|
|
| |
|
|
| |
E01 | Over current event while at | • Inverter output was | |
constant speed | • Motor shaft is locked | ||
| |||
|
| • Load is too heavy | |
E02 | Over current event during | ||
• A | |||
deceleration | incorrectly | ||
|
| Note: The L2002 will over current trip at | |
E03 | Over current event during | ||
nominally 200% of rated current | |||
| acceleration |
| |
E04 | Over current event for other | • DC braking power(A054) set too high | |
| conditions | • Current transformer / noise error | |
E05 | Overload protection | • Motor overload is detected by the | |
|
| electronic thermal function | |
E07 | Over voltage protection | • DC bus voltage exceeds a threshold, | |
|
| due to regenerative energy from motor | |
E08 | EEPROM error | • | |
|
| enced noise, high temperature, etc. | |
E09 | • DC bus voltage decreased enough to | ||
|
| cause a control circuit fault | |
E11 | CPU error | • | |
|
| ||
E22 |
|
| |
|
|
| |
E12 | External trip | • [EXT] input signal detected | |
|
| ||
|
|
| |
E13 | USP (Unattended Start | • When (USP) was enabled, an error | |
Protection) | occurred when power was applied while | ||
| |||
|
| a Run signal was present | |
|
|
| |
E14 | Ground fault | • A ground fault was detected between | |
| the inverter output and the motor. This | ||
|
| ||
|
| feature protects the inverter, and does not | |
|
| protect humans. | |
|
|
| |
E15 | Input | • Input voltage was higher than specified | |
| value, after 60 sec. in Stop Mode | ||
|
| ||
|
|
| |
E21 | Inverter thermal trip | • Inverter internal temperature is above | |
| the threshold | ||
|
| ||
|
|
| |
E30 | Driver error | • Inverter internal error, electrical noise | |
|
| at |
13