Hitachi series inverter manual Func Default Set Name / Description Value Code

Models: series inverter

1 34
Download 34 pages 32.7 Kb
Page 21
Image 21

Func.

 

Default

Set

Name / Description

Value

Code

Value

 

–FE(F)/–FU

 

 

 

 

 

 

 

 

 

 

A003/

Base frequency setting

50.0

/ 60.0

 

A203

 

 

 

 

 

 

 

 

 

A004/

Maximum frequency setting

50.0

/ 60.0

 

A204

 

 

 

 

 

 

 

 

A005

[AT] selection

00

 

 

• 00 Select between [O] and [OI] at [AT]

 

 

 

 

• 01 [O]+[OI] ([AT] input is ignored)

 

 

 

 

• 02 Select between [O] and keypad pot

 

 

 

 

• 03 Select between [OI] and keypad pot

 

 

 

 

 

 

 

A011

Pot./O–L input active range start frequency

0.0

 

 

 

 

 

A012

Pot./O–L input active range end frequency

0.0

 

 

 

 

 

 

A013

Pot./O–L input active range start voltage

 

0.

 

 

 

 

 

A014

Pot./O–L input active range end voltage

100.

 

 

 

 

 

A015

Pot./O–L input start frequency enable

01

 

 

• 00 Use A011 starting value)

 

 

 

 

• 01 Use 0 Hz

 

 

 

 

 

 

 

 

A016

External frequency filter time constant

2.

/ 8.

 

 

 

 

 

 

A020/

Multi-speed frequency setting

 

0

 

A220

 

 

 

 

 

 

 

 

 

A021

Multi-speed frequency settings (for both motors)

0.0

/ 0.0

 

A022

 

0.0

/ 0.0

 

A023

 

0.0

/ 0.0

 

A024

 

0.0

/ 0.0

 

A025

 

0.0

/ 0.0

 

A026

 

0.0

/ 0.0

 

A027..

 

......

 

..A035

 

0.0

/ 0.0

 

 

 

 

 

A038

Jog frequency setting

1.00

 

 

 

 

 

A039

Jog stop mode

00

 

 

• 00 Free-run stop, jogging disabled during

 

 

 

 

motor run

 

 

 

 

• 01 Controlled deceleration, jogging disabled

 

 

 

 

during motor run

 

 

 

 

• 02 DC braking to stop, jogging disabled

 

 

 

 

during motor run

 

 

 

 

 

 

 

A041/

Torque boost select

00

 

A241

• 00 Manual torque boost

 

 

 

 

• 01 Automatic torque boost

 

 

 

 

 

 

 

A042/

Manual torque boost value

5.0(A042)/

 

A242

 

0.0 (A242)

 

 

 

 

 

A043/

Manual torque boost frequency adjustment

3.0/(A043)

 

A243

 

0.0(A243)

 

 

 

 

 

 