Caution: Be sure to read the L2002 Inverter Manual and follow its Cautions and Warnings for the initial product installation. This Quick Reference Guide is intended for reference use by experienced users in servicing existing installations.

UL® Cautions, Warnings, and Instructions

Wiring Warnings for Electrical Practices and Wire Sizes

The Cautions, Warnings, and instructions in this section summarize the procedures necessary to ensure an inverter installation complies with Underwriters Laboratories® guidelines.

Warning: “Use 60/75°C Cu wire only” or equivalent.

Warning: “Open Type Equipment.”

Warning: “Suitable for use on a circuit capable of delivering not more than 100,000 rms symmetrical amperes, 240 V maximum.” For models with suffix N or L.

Warning: “Suitable for use on a circuit capable of delivering not more than 100,000 rms symmetrical amperes, 480 V maximum.” For models with suffix H.

Warning: “Hot surface—risk of burn.”

Warning: “Install device in pollution degree 2 environment.”

Warning: “Maximum Surrounding Air Temperature 50°C.”

Warning: “Risk of electric shock—capacitor discharge time is at least 5 minutes.”

Warning: “Solid state motor overload protection is provided in each model.”

Warning: “Tightening torque and wire range for field wiring terminals are marked adjacent to the terminal or on the wiring diagram.”

1

Page 3
Image 3
Hitachi series inverter UL Cautions, Warnings, and Instructions, Wiring Warnings for Electrical Practices and Wire Sizes