400V Models

Motor output

Inverter Model

Ampere Rating for

 

 

kW

HP

 

Fuse or Breaker

 

 

 

 

 

 

 

 

 

 

0.4

1/2

–004HFE(F)2/HFU2

3

 

 

 

 

0.75

1

–007HFE(F)2/HFU2

6

 

 

 

 

1.5

2

–015HFE(F)2/HFU2

10

 

 

 

 

2.2

3

–022HFE(F)2/HFU2

10

 

 

 

 

3.0

4

–030HFE(F)2

15

 

 

 

 

4.0

5

–040HFE(F)2/HFU2

15

 

 

 

 

5.5

7 1/2

–055HFE(F)2/HFU2

20

 

 

 

 

7.5

10

–075HFE(F)2/HFU2

25

 

 

 

 

Motor Overload Protection

Hitachi L2002 inverters provide solid state motor overload protection, which depends on the proper setting of the following parameters:

B012 “electronic overload protection”

B212 “electronic overload protection, 2nd motor”

Set the rated current [Amperes] of the motor(s) with the above parame- ters. The setting range is 0.2 * rated current to 1.2 * rated current.

Warning: When two or more motors are connected to the inverter, they cannot be protected by the electronic overload pro- tection. Install an external thermal relay on each motor.

4

Page 6
Image 6
Hitachi series inverter manual Motor Overload Protection