CHAPTER5 CANOPEN COMMUNICATION FUNCTION

5.1.7 Status word (Index: 6041h)

The status word indicates the current state of the inverter.

 

 

 

 

 

Bit

Description

 

 

 

 

 

 

 

Note

 

0

Ready to switch on

 

 

 

 

 

 

Mandatory

 

1

Switched on

 

 

 

 

 

 

 

Mandatory

 

2

Operation enabled

 

 

 

 

 

 

Mandatory

 

3

Fault

 

 

 

 

 

 

 

Mandatory

 

4

Voltage enabled

 

 

(~V1.04) Voltage disable -> enabled

 

Mandatory

 

5

Quick stop

 

 

 

 

 

 

 

Mandatory

 

6

Switch on disabled

 

 

 

 

 

 

Mandatory

 

7

Warning

 

 

 

 

 

 

 

Unsupported

 

8

Manufacturer Specific

 

 

 

 

 

 

Unsupported

 

9

Remote

 

 

 

 

 

 

 

Mandatory

 

10

Target reached

 

 

 

 

 

 

 

Mandatory

 

11

Internal Limit Active

 

“Index 6046” influences this bit.

 

Mandatory

 

12

(reserved)

 

 

(reserved)

 

 

 

Mode Specific

 

13

(reserved)

 

 

(reserved)

 

 

 

Mode Specific

 

14

Moving forwards

 

 

 

 

 

 

 

 

 

 

15

Moving backwards

 

 

 

 

 

 

 

 

Bitmapping of Status word

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Bit 6

 

Bit 5

 

Bit 3

Bit 2

Bit 1

 

Bit 0

 

Inverter

 

 

 

 

 

 

 

 

 

 

 

 

 

Switch On

 

Quick

 

Fault

Operation

Switch On

 

Ready to

 

 

 

 

 

 

 

 

 

 

 

Disable

 

Stop

 

Enable

 

Switch On

 

 

 

 

 

 

 

 

 

 

Not Ready to

 

0

 

X

 

0

0

0

 

0

 

Switch On

 

 

 

 

 

 

 

 

 

 

 

 

Switch On

 

1

 

X

 

0

0

0

 

0

 

Disabled

 

 

 

 

 

 

 

 

 

 

 

 

Ready to

 

0

 

1

 

 

0

0

0

 

1

 

Switch On

 

 

 

 

 

 

 

 

 

 

 

 

Switched On

 

0

 

1

 

 

0

0

1

 

1

 

Operation Enabled

 

0

 

1

 

 

0

1

1

 

1

 

Fault

 

0

 

X

 

1

1

1

 

1

 

Fault Reaction

 

0

 

X

 

1

1

1

 

1

 

Active

 

 

 

 

 

 

 

 

 

 

 

 

Quick Stop

 

0

 

0

 

 

0

1

1

 

1

 

‘X’ means that any value is allowed.

15

Page 19
Image 19
Hitachi SJ2-CO instruction manual Status word Index 6041h