CHAPTER6 COUNTERMEASURE FOR ABNORMALITY

6.4 LED display and Countermeasure

Following states are indicated by Module LED and CANopen status LED.

MOD (Module status) LED: It indicates Inverter condition.

CAN (CANopen status) LED: it indicates CANopen status.

LED

Color

 

State

 

 

Countermeasure

 

Category

 

Green ON

The inverter is in Normal

-

 

 

 

 

 

Mandatory

 

 

condition.

 

 

 

 

 

 

 

 

 

Green

The inverter is in Stand-by

-

 

 

 

 

 

Mandatory

 

single flash

condition.

 

 

 

 

 

 

 

 

 

Red ON

An

abnormality

occurred

Need to fix the inverter.

 

 

Mandatory

 

which is impossible to restore.

 

 

MOD

 

An

abnormality

occurred

When

in trip, remove

the

trip

 

 

 

which is possible to restore.

causes.

 

 

 

 

 

 

Red single

Mostly this state occurs, when

 

the

inverter

 

 

the inverter is in trip condition.

When

initializing,

Mandatory

 

flash

starts

up

automatically

the

 

But except status below.

 

 

 

BOOTUP

process

after

the

 

 

 

User initializing with b084 set

 

 

 

to 01 or 02.

 

initializing.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

Power off

 

-

 

 

 

 

 

Mandatory

 

Green ON

OPERATIONAL

 

-

 

 

 

 

 

Mandatory

 

Green

STOPPED

 

-

 

 

 

 

 

Mandatory

 

single flash

 

 

 

 

 

 

 

Green

PRE-OPERATINAL

 

-

 

 

 

 

 

Mandatory

 

Blinking

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CAN

OFF

no error

 

-

 

 

 

 

 

Mandatory

 

Red single

Warning limit reached

Any Flaming error

 

 

 

Mandatory

 

flash

 

 

 

 

 

 

 

 

 

 

 

Red double

 

 

 

The Guarding Protocol or the

 

 

Error Control Event

 

Heartbeat

Protocol

 

is

Mandatory

 

flash

 

 

 

processing.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

notes

LED ON: constantly on

LED OFF: constantly off

LED blinking:

iso-phase on and off with a frequency of approximately 2.5Hz: on for approximately 200ms and off for approximately 200ms.

LED single flash:

one short flash (approximately 200ms) followed by a long off phase (approximately 1000ms). LED double flash:

a sequence of two short flashes (approximately 200ms), separated by an off phase (approximately 200ms).

The sequence is finished by a long off phase (approximately 1000ms).

22

Page 26
Image 26