3-14. Selecting A Location And Connecting Input Power

!

Do not move or operate unit where it could tip.

18 in (457 mm) of space for airflow

1

8

=GND/PE Earth Ground

10

7

9

6

L1

5

L2

 

4

2

3

 

1

L2L1

230 VAC, 1

Ref. 242 691-A / 802 286-E

! Installation must meet all National and Local Codes − have only quali- fied persons make this installation.

! Special installation may be

required where gasoline or volatile liquids are present − see NEC Ar- ticle 511 or CEC Section 20.

! Disconnect and lockout/tagout in- put power before connecting input

conductors from unit.

! Always connect green or green/yel- low conductor to supply grounding terminal first, and never to a line

terminal.

1 Rating Label

Supply correct input power.

2Plug (NEMA Type 6-50P)

3Receptacle NEMA Type 6-50R) Connect plug to receptacle.

4Input Power Cord.

5Black And White Input Conductor (L1 And L2)

6Green Or Green/Yellow Grounding Conductor

7Disconnect Device (switch shown in the OFF position)

8Disconnect Device Grounding Terminal

9 Disconnect Device Line Terminals

Connect green or green/yellow grounding conductor to disconnect device grounding terminal first.

Connect input conductors L1 and L2 to dis- connect device line terminals.

10 Over-Current Protection

Select type and size of over-current protection using Section 3-13(fused dis- connect switch shown).

Close and secure door on disconnect device. Remove lockout/tagout device, and place switch in the On position.