4-10. Serial Number And Rating Label Location

The serial number and rating information for this product is located on the back. Use rating label to determine input power requirements and/or rated output. For future reference, write serial number in space provided on back cover of this manual.

4-11. Connecting 1-Phase Input Power For 240 VAC

!

Installation must meet all National and Local Codes have only qualified persons make this installation.

1

! Disconnect and lockout/tagout input power before connecting input conductors from unit.

5

7

4

6

L1

L2

2

3

=GND/PE Earth Ground

1

! Always connect green or green/ yellow conductor to supply grounding terminal first, and never to a line terminal.

1Black And White Input Conductor (L1 And L2)

2Green Or Green/Yellow Grounding Conductor

3Input Power Cord.

4Disconnect Device (switch shown in the OFF position)

5Disconnect Device Grounding Terminal

6Disconnect Device Line Terminals

Connect green or green/yellow grounding conductor to disconnect device grounding terminal first.

Connect input conductors L1 and L2 to disconnect device line terminals.

7Over-Current Protection

8

 

L2

L1

240 VAC, 1

Select type and size of over-current protection using Section 4-8 (fused disconnect switch shown).

8Receptacle (NEMA 6-50R) Customer Supplied

Close and secure door on disconnect device. Remove lockout/tagout device, and place switch in the On position.

Tools Needed:

803 766-B / Ref. 802 443-A

OM-244 013 Page 15