2-12. Electrical Service Guide
Input Voltage | 200 | 230 | 460 | 575 | |
|
|
|
|
| |
Input Amperes At Rated Output | 50 | 44 | 22 | 17 | |
|
|
|
|
| |
Max Recommended Standard Fuse Or Circuit Breaker Rating In | 80 | 70 | 35 | 25 | |
Amperes | |||||
|
|
|
| ||
|
|
|
|
| |
Min Input Conductor Size In AWG/Kcmil | 8 | 8 | 10 | 12 | |
|
|
|
|
| |
Max Recommended Input Conductor Length In Feet (Meters) | 93 (28) | 124 (38) | 329 (100) | 313 (95) | |
|
|
|
|
| |
Min Grounding Conductor Size In AWG/Kcmil | 8 | 8 | 10 | 12 | |
|
|
|
|
| |
Reference: 1996 National Electrical Code (NEC) |
|
|
| ||
|
|
|
|
|
2-13. Selecting A Location And Connecting Input Power
Have only qualified persons make this installation.
1 Rating Label
Supply correct input power.
Y Special installation may be required where gasoline or volatile liquids are present – see NEC Article 511 or CEC Section 20.
18 in (457 mm) for airflow
GND/PE
Connect First L1
1
GND/PE
L2
Size and ratings must comply with ap- plicable codes. Install conductors in conduit or equivalent into a deener- gized line disconnect device (see Section
801