R4795A

Flame Safeguard

Primary Controls

The R4795A Protectorelay™ Primary Control provides solid state electronic flame safeguard protection for commercial and industrial gas or oil burners. It provides a prepurge period before each start, and intermittent pilot.

120V models meet the requirements of Underwrit- ers Laboratories Inc. Standard 795 for mechanical draft and atmospheric burner inputs from 400,000 to 2,500,000 Btu.

Meets Underwriters Laboratories Inc. requirements for oil burner group 8 when 30, 60, or 90 second pre- purge timer is used.

Selection of solid state, plug-in prepurge timers pro- vides 7, 10, 30, 60, or 90 second prepurge time.

Includes terminals for connection of air flow switch to prove airflow before prepurge period starts, dur- ing purge, and during the entire Run period.

Choice of interchangeable, color-coded, solid state, plug-in flame signal amplifiers allows use with rec- tification or ultraviolet type flame detectors.

Safe-start feature prevents start when flame or flame simulating condition is present.

Recycles through prepurge if the flame goes out while burner is running. If pilot flame is not re- established, safety switch trips and locks out system.

A tripped safety switch must be manually reset to restore operation.

Push-to-reset safety switch is dust-resistant enclosed.

Optional spdt alarm contacts operate external alarm on safety switch lockout.

Ignition interference circuit (rectification amplifier only) protects electronic network from high voltage ignition crossover and provides visual indication when interference occurs.

Solid state circuitry eliminates vacuum tube replace- ment and increases resistance to vibration. Applica- tion of power not required during Off cycle; no tube warmup before starting.

Easy-to-replace plug-in components result in faster service and reduced inventory.

Flame current jack, located on the amplifier, provides means of plugging in a microammeter to measure the flame signal with system operating.

Easy mounting and removal through use of captive mounting screws, which also serve as electrical connections.

Durable thermoplastic mounting base.

Models available with -40°F (-40°C) temperature rating.

CONTENTS

 

Specifications

2

Ordering Information

2

Installation

4

Checkout

8

Operation

11

Troubleshooting

11

Service

13

S.Y. • Rev. 12-94 • ©Honeywell Inc. 1994

1

6060-2285--77

Page 1
Image 1
Honeywell specifications R4795A Flame Safeguard Primary Controls