Honeywell R4795A specifications Terminal, Load, Rating

Models: R4795A

1 16
Download 16 pages 24.8 Kb
Page 3
Image 3
Terminal

R4795A

SPECIFICATIONS

TERMINAL RATINGS:

 

 

 

 

Terminal

Load

 

Rating

 

 

 

 

3

Pilot Valve

125

VA pilot duty.

 

 

 

 

 

Intermittent Ignitiona

360

VA.

4

Interrupted Ignition

360

VA.

 

 

 

 

5

Main Fuel Valve(s)

125

VA pilot duty, or 25 VA pilot duty plus one or more motorized

 

 

valves with total rating up to 400 VA opening, 200 VA holding.

 

 

 

6-7

Airflow Switch

0.6A at 30 Vdc.

 

 

 

8

Fan or Burner Motor

9.8A full load, 58.8A locked rotor (inrush) at 120 Vac. 4.9A full

 

 

load, 29.4A locked rotor (inrush at 220 and 240 Vac.

 

 

 

Isolated Spdt Alarm

Alarm

3A at 24 volts, or 1A at 120 volts, in a suitable wiring enclosure.

Terminals (Optional)

 

 

 

 

 

 

 

aWhen ignition is connected to terminal 3, terminal 4 cannot be used.

NOTE: Allowable inrush can be up to ten times the pilot duty rating.

Example:

Pilot duty rating = 125 VA.

At 120V, running current is 125/120 = 1.05A. Maximum allowable inrush is 10 times 1.05 = 10.5A.

DIMENSIONS (Includes Cover and Subbase): Approxi- mately 5 x 5 x 5 in. (127 x 127 x 127 mm).

MOUNTING: Q270A1024 Subbase. Ordered separately.

APPROVALS:

Underwriters Laboratories Inc Listed: 120V models us- ing 30, 60, or 90 second prepurge timers including – 40°F (–40°C) rated models; file no. MP268, guide no. MCCZ.

Underwriters Laboratories Inc. Component Recognized: 120 volt models using 7 or 10 second prepurge timers including -40°F (-40°C) rated models; file no. MP268, guide no. MCCZ2.

Canadian Standards Association Certified: 120V mod- els only, including -40°F (-40°C) rated models; file no. LR95329.

Factory Mutual Approved: R4795A 120V models; re- port no. 18774. -40°F (-40°C) rated models; report no. 19608.1.

American Gas Association Design Certified: File no. 21-6 (F and F1).

ACCESSORIES:

W136A Test Meter (includes 117053 Meter Connector Plug).

Flame Simulator: 203659 Ultraviolet 121708 Rectification 123514B Ultraviolet

117053 Meter Connector Plug FSP1535 Tester for operational check Q624 Solid State Spark Generator

118702E Remote Reset Cover, 120 Vac, 60 Hz

202471C Reset Cover for R4795A

ADDITIONAL CONTROLS:

Order all additional controls separately:

Q270A1024 Mounting Subbase.

Plug-In Flame Signal Amplifiers, Rectification Type (Green Backplate): For use with C7004B C7005A, and B, C7008A, or Q179A,C Rectifying Flame Rods (for gas); C7003A, C7010A, C7013A or C7014A Photocells (for oil); or C7012A,C Purple Peeper Ul- traviolet Flame Detectors (for gas or oil).

R7289A1004 Amplifier: 3 sec nominal flame failure response.

R7289A1012 Amplifier: 0.8 sec nominal flame failure response.

R7289A1020 Amplifier: 3 sec nominal flame failure response, -40°F (-40°C) ambient temperature.

Ultraviolet Type (Purple Backplate): For use with C7027A, C7035A or C7044A Minipeeper Ultraviolet Flame Detectors (for gas or oil).

R7290A1001 Amplifier: 3 sec nominal flame failure response.

R7290A1019 Amplifier: 0.8 sec nominal flame failure response.

R7290A1027 Amplifier: 3 sec nominal flame failure response, -40°F (-40°C) ambient temperature.

ST71A Plug-In Prepurge Timer (ordered separately): Minimum Timings: 7, 10, 30, 60, and 90 seconds (as

ordered).

Maximum Timings: 8.4, 12, 36, 72, and 108 seconds at room ambient temperature.

Recommended Limits: L404A; L604A,L; L4006A,C,E; L4008A,E,F; L6006A,B: These controllers were Underwriters Laboratories Inc. tested for breaking loads only, at 120 Vac, for the total rating of 9.8A full load, plus 360VA ignition, plus 250 VA pilot duty.

Flame Detector: As specified in Plug-In Flame Signal Amplifiers listed above.

3

60-2285—7

Page 3
Image 3
Honeywell R4795A specifications Terminal, Load, Rating