R4795A
SPECIFICATIONS
TERMINAL RATINGS:
|
|
|
|
Terminal | Load |
| Rating |
|
|
|
|
3 | Pilot Valve | 125 | VA pilot duty. |
|
|
|
|
| Intermittent Ignitiona | 360 | VA. |
4 | Interrupted Ignition | 360 | VA. |
|
|
|
|
5 | Main Fuel Valve(s) | 125 | VA pilot duty, or 25 VA pilot duty plus one or more motorized |
|
| valves with total rating up to 400 VA opening, 200 VA holding. | |
|
|
| |
Airflow Switch | 0.6A at 30 Vdc. | ||
|
|
| |
8 | Fan or Burner Motor | 9.8A full load, 58.8A locked rotor (inrush) at 120 Vac. 4.9A full | |
|
| load, 29.4A locked rotor (inrush at 220 and 240 Vac. | |
|
|
| |
Isolated Spdt Alarm | Alarm | 3A at 24 volts, or 1A at 120 volts, in a suitable wiring enclosure. | |
Terminals (Optional) |
|
|
|
|
|
|
|
aWhen ignition is connected to terminal 3, terminal 4 cannot be used.
NOTE: Allowable inrush can be up to ten times the pilot duty rating.
Example:
Pilot duty rating = 125 VA.
At 120V, running current is 125/120 = 1.05A. Maximum allowable inrush is 10 times 1.05 = 10.5A.
DIMENSIONS (Includes Cover and Subbase): Approxi- mately 5 x 5 x 5 in. (127 x 127 x 127 mm).
MOUNTING: Q270A1024 Subbase. Ordered separately.
APPROVALS:
Underwriters Laboratories Inc Listed: 120V models us- ing 30, 60, or 90 second prepurge timers including – 40°F
Underwriters Laboratories Inc. Component Recognized: 120 volt models using 7 or 10 second prepurge timers including
Canadian Standards Association Certified: 120V mod- els only, including
Factory Mutual Approved: R4795A 120V models; re- port no. 18774.
American Gas Association Design Certified: File no.
ACCESSORIES:
W136A Test Meter (includes 117053 Meter Connector Plug).
Flame Simulator: 203659 Ultraviolet 121708 Rectification 123514B Ultraviolet
117053 Meter Connector Plug FSP1535 Tester for operational check Q624 Solid State Spark Generator
118702E Remote Reset Cover, 120 Vac, 60 Hz
202471C Reset Cover for R4795A
ADDITIONAL CONTROLS:
Order all additional controls separately:
Q270A1024 Mounting Subbase.
R7289A1004 Amplifier: 3 sec nominal flame failure response.
R7289A1012 Amplifier: 0.8 sec nominal flame failure response.
R7289A1020 Amplifier: 3 sec nominal flame failure response,
Ultraviolet Type (Purple Backplate): For use with C7027A, C7035A or C7044A Minipeeper Ultraviolet Flame Detectors (for gas or oil).
R7290A1001 Amplifier: 3 sec nominal flame failure response.
R7290A1019 Amplifier: 0.8 sec nominal flame failure response.
R7290A1027 Amplifier: 3 sec nominal flame failure response,
ST71A
ordered).
Maximum Timings: 8.4, 12, 36, 72, and 108 seconds at room ambient temperature.
Recommended Limits: L404A; L604A,L; L4006A,C,E; L4008A,E,F; L6006A,B: These controllers were Underwriters Laboratories Inc. tested for breaking loads only, at 120 Vac, for the total rating of 9.8A full load, plus 360VA ignition, plus 250 VA pilot duty.
Flame Detector: As specified in
3 |