
Switch Definitions and Terminology
Pressure/Vacuum Switch - A device that senses a change in pressure/ vacuum and opens or closes an electrical circuit when the set point is reached.
Set Point - The
Electrical Contacts - The elements in the switch that electrically respond to the media applied to the actuator. Snap action contacts with a
Pressure Switch Actuator - The member in the switch which receives the media and ultimately strokes the electrical contacts to open or close at the designated set point. The actuator in the Series III is a beryllium copper or silicone rubber diaphragm. An elastomeric diaphragm or piston actuator is used in the Series V.
The 5000 Series uses a polyimide film diaphragm.
Normally Open
Normally Closed
-A normally closed switch conducts electricity until the actuator is moved by the media causing the contacts to open.
Dual Circuit (SPDT) - A normally open and normally closed circuit are contained in a switch.
Dual Circuit (N.O./N.O.) - Switch contains two normally open circuits.
Dual Circuit (N.C./N.C.) - Switch contains two normally closed circuits.
System Pressure/Vacuum - This is the normal pressure/vacuum that would be present at the switch actuator. This value is important in order to apply the proper switch configuration. Even though the set point may be relatively low, the system pressure would continue to be applied to the switch actuator in most cases.
Proof Pressure - This specification is the maximum
Burst Pressure - This specification is the maximum over pressure condition that the switch can withstand without experiencing leakage.
Dry Circuit Load - Typically this would be a very low electrical load associated with microprocessors when the open circuit voltage is .03V or less and the current is 40mA or less.
Resistive Load - A load in which the voltage is in phase with the current.
Inductive Load - A load in which the voltage leads the current.
Motor Load - The load of a motor at rated horsepower and speed.
Capacitive Load - A load which the current leads the voltage.
Differential - The difference between opening (actuation) pressure and the closing
Conversion Factors
|
|
|
|
|
| Convert | To | Multiply By | |
|
|
|
|
|
| kPa | PSI | .145 |
|
| PSI | kPa | 6.8948 |
|
| BARS | PSI | 14.5 |
|
| PSI | BARS | .069 |
|
| Hg” | PSI | .4912 |
|
| PSI | Hg” | 2.036 |
|
| H2O” | PSI | .03613 |
|
| PSI | H2O” | 27.6778 |
|
| H2O” | Hg” | .07355 |
|
| Hg” | H2O” | 13.5962 |
|
| C° | F° | 1.8(C° +17.78) | |
| F° | C° |
| |
|
|
|
|
|
10