T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
33 63-4368
S7760 - Command DisplayA network connected Command display can be configured (by
LonSpec) to implement the following T7350H functions:
View and Modify Schedules:
• Occupied, Unoccupied and Standby setpoints1
• weekly schedule
• holiday schedule
NOTE: If a T7350H is connected to a wall module with set-
point adjustment, the user will not be allowed to
change occupied setpoints through Command Dis-
play.
Command manual occupancy, Annunciate T7350H alarms,
Monitor T7350H data:
• Room Temperature
• Active Room Temperature SetPoint
• Occupancy Status
• Operating Mode
• Discharge Air Temperature
• Space Humidity
• Outdoor Temperature
• Heat Stages Active
• Cool Stages Active
• Heat Modulating Output Position
• Cool Modulating Output Position
• Bypass Minutes Remaining
• Auxiliary Relay Status
• Fan Status
XL15C
Application Object Application Input
Source T7350H
Network Variable Network Variable Field
nvoAlarmStatus InvalidSubBaseType
nvoError errLoclSpaceSensr
nvoError ErrRemtSpaceSensr
nvoError ErrNetSpaceSensr
nvoError ErrLoclHumSensr
nvoError ErrRemtHumSensr
nvoError errNetHumSensr
nvoError ErrRemtOdSensr
nvoError ErrNetOdSensr
nvoError ErrRemtSetPt
nvoError ErrDischSensr
nvoError errIOConfig
nvoError errSubBaseType
nvoError errSubBaseVerMisMatch
nvoError errNviSpaceTemp
nvoError errNviOccSchedule
nvoError errNviOccSensor
nvoError errnviApplicMode
nvoError errnviOutdoorTemp
nvoError errnviSpaceRH
nvoError errNviBypass
nvoError errNviDLCShed
nvoData2 RelayHeat3
nvoData2 RelayCool3
nvoData2 RelayHeat2
nvoData2 RelayCool2
nvoData2 RelayAux
nvoData2 RelayHeat1
nvoData2 RelayCool1
nvoData2 RelayFan
nvoData2 dehumidActive
Table 20. Network Connections to XL15C AP Inputs. (Continued)
T7350H Network Variable Outputs can be used as inputs to XL15C application objects.