T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
43 63-4368
Table 21. T7350H Network Variable Summary. (Continued)
Nv Name LONSPEC™ Ref Name Class Description
nvoUnitStatus Unit Status OUT Unit Status:
Percentage of cooling capability currently being supplied to the
controlled space.
163.84: Power up value.
Fan turned on or off:
0: Fan not running.
100: Fan running.
163.84: (power up value).
Percentage of auxiliary heating capability currently being supplied
to the controlled space (Applies to heat pump application only):
163.84: Power up value.
Alarm report:
0: No alarms reported in the unit (power up value).
1: One or more alarms reported in the unit.
-1: The Alarms have been suppressed by alarm notified
disabled command.
Effective operating mode:
0: HVAC_AUTO (power up value).
1: HVAC_HEAT
3: HVAC_COOL
6: HVAC_OFF (power up value).
7: HVAC_TEST (manual mode or cover in factory test mode).
8: HVAC_EMERG_HEAT