B. Sequence of Operation
1. Sequence Cycles and Shutdown
The steps in the sequence are as outlined below.
Note: 1. There is a slight delay at startup.
2.When power is turned on, the
3.There is a
4.EvapFM
5.A
6.On freezers, EvapFM is
a)Refrigerator
1. Startup/Cool Down
EvapFM and MH energize. There is a slight delay before cabinet temperature or high‑temperature alarm (Hi) appears on DM and Comp and ConFM energize.
2.Cool Down Achieved
CM monitors cooling of the cabinet via CTh. CTh cools to 3°F (1.7°C) below setpoint. EvapFM and MH continue. Comp and ConFM
3.Cool Down Restart
CTh warms to 3°F (1.7°C) above setpoint. EvapFM and MH continue. Comp and ConFM energize.
4.Defrost
"dEF" is displayed during defrost. There is a
a)Temperature Initiation: When DTh cools to 8.6°F
b)Manual Initiation: Manual defrost may be initiated by pressing and holding the lower button until "dEF" appears on DM. EvapFM and MH continue. Comp and ConFM de‑energize.
c)Termination: DTh warms to 40°F (4.4°C). EvapFM and MH continue. Comp and ConFM energize,
Note: There is a
Legend: