2. Alarm Safeties
Alarm signals are designed to protect the unit and food product. These alarms give information or warnings in the event the unit is operating out of acceptable parameters. Should one of the alarms occur, follow the instructions in the table below to address the alarm. The alarm code flashes once every second with audible alarm. To silence the alarm, press and release the upper button.
Alarm Signals
Alarm Code | Problem | Corrective Action/Reset Details | |
|
|
| |
| Cabinet Thermistor Malfunction Alarm | Cabinet thermistor disconnected, shorted, or open. | |
|
| Check connection and continuity. Reconnect or | |
E1 | Cabinet thermistor has failed. | replace as needed. | |
|
| Unit cycles 5 min. on, | |
|
|
| |
| Defrost Thermistor Malfunction Alarm | Defrost thermistor disconnected, shorted, or open. | |
E2 |
| Check connection and continuity. Reconnect or | |
| Defrost thermistor has failed. | replace as needed. | |
|
| Unit cycles on and off with cabinet thermistor. | |
|
|
| |
UHi | The compressor | ||
more) | operates. The voltage safeties automatically reset | ||
| |||
|
| when voltage is corrected. | |
ULo | |||
| First try obvious corrections such as closing doors | ||
| Note: When power is turned on, the | and cleaning the condenser. | |
|
| ||
| bypassed. Therefore, a | Automatically resets when temperature returns to | |
| alarm can occur at startup. | normal. | |
Hi | Refrigerator: Cabinet temperature has |
| |
| exceeded the setpoint temperature by |
| |
| 10°F (5.6°C) for more than 2 hours. |
| |
| Freezer: Cabinet temperature has |
| |
| exceeded the setpoint temperature by |
| |
| 27°F (15°C) for more than 2 hours. |
| |
|
|
| |
| Automatically resets when temperature returns to | ||
|
| normal. | |
Lo | Refrigerator & Freezer: Cabinet |
| |
| temperature has remained below the |
| |
| setpoint temperature by 8°F (4.4°C) for |
| |
| more than 2 hours. |
| |
|
|
| |
| Communication Error Alarm | Check the connections at the control module | |
|
| and the display module. If connections are good, | |
E13 | Communication between the control | the control module and display module must be | |
module and the display module has been | replaced. | ||
| |||
| interrupted or disconnected. |
| |
|
| The unit operates on a set | |
|
| off cycle until communication is restored. | |
| Compressor Off | Unit (compressor) off. | |
"– – |
| Press and hold the upper and lower buttons until the | |
|
| ||
|
| temperature appears on the display. | |
|
|
|