F. Water Supply and Drain Connections
See Fig. 3
CAUTION
To prevent damage to the equipment, do not operate this icemaker when the water supply is off, or if the pressure is below 10 PSIG. Do not run the icemaker until the proper water pressure is reached.
•Water supply inlet is 1/2" female pipe thread (FPT).
•A water supply line
•Water supply pressure should be a minimum of 10 PSIG and a maximum of 113 PSIG. If the pressure exceeds 113 PSIG, the use of a pressure reducing valve is required.
•The minimum recommended drain line is 3/4" nominal hard pipe.
•Drain outlets are 3/4" FPT.
•Drain lines must have 1/4" fall per foot (2 cm per 1 m) on horizontal runs to get a good flow. A vented tee connection is also required for proper flow.
•Drain lines should not be piped directly to the sewer system. An air gap of a minimum of 2 vertical inches (5 cm) should be between the end of the drain pipes from the icemaker and the floor drain.
•This icemaker must be installed in accordance with applicable national, state, and local regulations.
•A plumbing permit and services of a licensed plumber may be required in some areas.
Water Supply Line
Minimum 3/8" Nominal Copper Water Tubing
|
|
|
|
|
|
|
| Drain Valve |
|
|
| Minimum 3/4" Nominal Hard Pipe | |||||
(5 cm) air gap |
|
|
| |||||
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Floor | Piping to |
Drain | approved drain. |
Water Supply Inlet 1/2" FPT
Bin Drain Outlet 3/4" FPT
Drip Tray
Drain Outlet
3/4" FPT
Fig. 3
9