F. Electrical Connection

F. Electrical Connection

KM-1400SWH-MWARNING

1.Electrical connection must be hard-wired and must meet international, national, state, and local electrical code requirements. Failure to meet these code requirements could result in death, electric shock, serious injury, fire, or severe damage to equipment.

2.This unit requires an independent power supply. See the nameplate for proper voltage and breaker/fuse size. Failure to use a proper breaker or fuse can result in a tripped breaker, blown fuses, or damage to existing wiring. This could lead to heat generation or fire.

3.THIS UNIT MUST BE GROUNDED. Failure to properly ground this unit could result in death or serious injury.

4.Electrical connection must be made in accordance with the instructions on the "WARNING" tag, provided with the pig tail leads in the junction box. See Fig. 8a and 8b.

Usually an electrical permit and services of a licensed electrician are required.

The maximum allowable voltage variation is ±10 percent of the nameplate rating.

The transformer's voltage tap switch must be positioned to match incoming voltage at startup.

CAUTION! On three phase models, connect the highest incoming voltage supply ("stinger leg") to the red power supply wire (red common wire to the compressor).

The opening for the power supply connection is 7/8" DIA to fit a 1/2" trade size conduit.

KM-1400SWH-M

Fig. 8a WARNING

ELECTRICAL CONNECTION

THIS UNIT MUST BE GROUNDED

Failure to properly ground or wire this unit could result in death, serious injury, or severe damage to the icemaker.

The transformer’s voltage tap switch must be positioned to match incoming voltage at startup.

See diagram below.

208-230/60/1

JUNCTION BOX

L1 BROWN

208-230V

L2 BLACK

Fig. 8a

KM-1400SWH3-M

KM-1400SWH3-M WARNING

ELECTRICAL CONNECTION

THIS UNIT MUST BE GROUNDED

Failure to properly ground or wire this unit could result in death, serious injury, or severe damage to the icemaker.

This unit must be connected to a three-phase power source.

The transformer’s voltage tap switch must be positioned to match incoming voltage at startup.

See diagram below.

208-230/60/3 JUNCTION BOX

 

 

 

 

 

 

L1

 

 

 

230V

 

208- 230V

 

 

BROWN

 

 

 

 

 

 

L2

 

 

 

 

 

 

 

 

 

 

-

 

 

 

 

RED

208

 

208- 230V

 

 

L3

 

 

 

 

 

 

 

 

 

BLACK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fig. 8b