b) Connection to a Closed Loop System
•Condenser water supply inlet is 1/2" female pipe thread (FPT). A minimum of 3/8" nominal copper water tubing is recommended for the condenser water supply line.
•Condenser return outlet is 3/8" FPT. A minimum of 3/8" nominal copper water tubing is recommended for the condenser return line.
•
•The water supply to the condenser should not drop below 4 GPM.
•The pressure differential between the condenser water supply inlet and condenser return outlet must be no less than 10 PSIG.
•When using a glycol blend, the solution mixture should be less than 30% glycol.
•In order to maintain the proper high side pressure, the condenser water supply inlet temperature should not drop below 45°F (7°C) and the condenser return outlet temperature must be in the 104°F to 115°F (40°C to 46°C) range. Once the icemaker installation is complete, confirm the condenser return outlet temperature 5 minutes after a freeze cycle starts. If the condenser return outlet temperature is not in the proper range, use a flat blade screwdriver to rotate the adjustment screw on the water‑regulating valve until the temperature is in the proper range (rotate counterclockwise to raise temperature or clockwise to lower temperature).
Minimum 3/8" Nominal Copper Water Tubing
Icemaker |
Water Supply |
Inlet |
1/2" FPT |
Condenser Water |
Supply Inlet |
1/2" FPT |
Condenser |
Return Outlet |
3/8" FPT |
Icemaker
Vent Tube
Minimum 1/2" Nominal Copper Water Tubing
Icemaker Water Supply Line
Icemaker Water Supply Line
Drain Valve
Condenser Water Supply Line
Condenser Water Supply Line Drain Valve
Condenser Return Line
Condenser Return Line Drain Valve
Icemaker | Bin |
Drain Outlet |
|
3/4" FPT |
|
Condensation |
|
Drain Outlet |
|
3/8" OD Hard Tube |
|
| Separate piping to approved drain. |
| Leave a |
| gap between the end of each pipe |
Minimum | and the drain. |
| |
3/4" Nominal |
|
Hard Pipe |
|
Vent Tube |
Bin Drain Outlet
See Manufacturer's Instructions
Floor Drain
Fig. 10 | |
| Connection to a Closed Loop System |
16