Hoshizaki KM-2000SRH3, KM2000SWF3, KM-2000SRF3, KM-2000SWH3 service manual

Models: KM-2000SWH3 KM-2000SRF3 KM-2000SRH3 KM2000SWF3

1 56
Download 56 pages 4.31 Kb
Page 45
Image 45
Manual background

10.REMOVAL AND REPLACEMENT OF CONDENSING PRESSURE REGULATOR (C.P.R.) - REMOTE AIR-COOLED MODEL ONLY

IMPORTANT

Always install a new Drier every time the sealed refrigeration system is opened. Do not replace the Drier until after all other repair or replacement has been made.

1)Turn off the power supply.

2)Remove the panels from the remote condenser unit.

3)Recover the refrigerant and store it in an approved container.

4)Before heating, break off the stub on the dome to release the dome charge.

5)Disconnect the C.P.R. using brazing equipment.

6)Install the new C.P.R. Use nitrogen gas at the pressure of 3-4 PSIG when brazing the C.P.R.

WARNING

Always protect the C.P.R. body by using a damp cloth to prevent the C.P.R. from overheating. Do not braze with the C.P.R. body exceeding 250°F.

7)Install the new Drier in the icemaker.

8)Check for leaks using nitrogen gas (140 PSIG) and soap bubbles.

9)Evacuate the system and charge it with refrigerant. See the Charge Label in the machine compartment in the icemaker.

10)Replace the panels in their correct positions.

11)Turn on the power supply.

45

Page 45
Image 45
Hoshizaki KM-2000SRH3, KM2000SWF3, KM-2000SRF3, KM-2000SWH3 service manual