Hoshizaki SRC-10H Electrical Connection, Installation of Remote Condensing Unit, b Location

Models: SRC-10H

1 25
Download 25 pages 2.61 Kb
Page 11
Image 11
5. Electrical Connection

5. Electrical Connection

This icemaker must have an independent power supply or receptacle of proper capacity. See the nameplate.

6. Installation of Remote Condensing Unit

[a] Checks Before Installation

1)Unpack and remove shipping carton, tape(s) and packing.

2)Check that the refrigerant lines do not rub or touch lines or other surfaces, and that the fan blade turns freely.

3)Make sure that the icemaker, line sets and remote condensing unit all use R-404A refrigerant.

[b] Location

The condensing unit must be positioned in a permanent site under the following guidelines.

A firm and flat site.

A dry and well ventilated area with 24" clearance on both front and rear for ease of maintenance and service should they be required.

Normal condenser ambient temperature: -4°F to +122°F. Temperatures not within this operating range may affect the production capacity of the icemaker.

The maximum line length is 55 feet. Vertical distance between the condensing unit and icemaker should not exceed 30 feet above or 10 feet below the icemaker.

Fig. 3

Note: If the recommended installation guidelines are not followed, icemaker performance may be reduced.

11

Page 11
Image 11
Hoshizaki SRC-10H Electrical Connection, Installation of Remote Condensing Unit, a Checks Before Installation, b Location