Minimum Rack

Requirements

Mounts in ProLiant, and Telco racks and Third Party racks that meet the following criteria:

Compatible with 19-inch Standard EIA rail sets

EIA rail-to-rail depth is 29 - 30"

Cabinet depth must be at least 36-inch deep overall (Additional min. 3.5-inch clearance from rear RETMA rail to rear door, inclusive in the 36-inch overall depth)

Ample room for top and bottom cable egress (approximately 8 square inches for full rack configuration with patch panel)

Must be capable of supporting 1600 lb (for full rack configuration)

Perforated front and rear doors to accommodate front-to-back cooling

Must have 65% open perforation on server blade enclosure doors to support airflow requirements

Optimized for use with the HP 10000 Series racks

NOTE: If using Compaq 7000 Series rack, Rack Extension Kit and High Air Flow Rack Door options are required.

Rack Airflow

Rack 10000 series Cabinets

Requirements

The increasing power of new high-performance processor technology requires increased cooling

 

efficiency for rack-mounted servers. The 10000 Series Racks provide enhanced airflow for maximum

 

cooling, allowing these racks to be fully loaded with servers using the latest processors.

 

CAUTION: If a third-party rack is used, observe the following additional requirements to ensure

 

adequate airflow and to prevent damage to the equipment:

 

Front and rear doors: If your 42U server rack includes closing front and rear doors, you must

 

allow 830 square inches (5,350 sq cm) of hole evenly distributed from top to bottom to permit

 

adequate airflow (equivalent to the required 64 percent open area for ventilation).

 

Side: The clearance between the installed rack component and the side panels of the rack must be

 

a minimum of 2.75 inches (7 cm).

 

CAUTION: Always use blanking panels to fill all remaining empty front panel U-spaces in the rack. This

 

arrangement ensures proper airflow. Using a rack without blanking panels results in improper cooling

 

that can lead to thermal damage.

 

NOTE: For additional information, refer to the Setup and Installation Guide or the Documentation CD

 

provided with the server, or to the server documentation located in the Support section at the following

 

URL: http://www.hp.com/servers/bl25p.

 

 

Factory Express Portfolio

HP Factory Express offers configuration, customization, integration and deployment services for HP

for Servers and Storage

servers and storage products. Customers can choose how their factory solutions are built, tested,

 

integrated, shipped and deployed.

 

Factory Express offers service packages for simple configuration, racking, installation, complex

 

configuration and design services as well as individual factory services, such as image loading, asset

 

tagging and custom packaging. HP products supported through Factory Express include: a wide array of

 

servers and storage: HP Integrity, HP ProLiant & HP ProLiant Server Blades, HP BladeSystem, HP 9000

 

servers as well as the MSA1000, VA7xxx, EVA3000 & EVA5000, XP, rackable tape libraries and

 

configurable network switches.

 

For more information on Factory Express services for your specific server model please contact your sales

 

representative or go to http://www.hp.com/go/factory-express.

 

 

DA - 12160 North America — Version 7 — June 27, 2005

Page 19

Page 19
Image 19
HP 275 manual Minimum Rack Requirements, Rack Airflow Rack 10000 series Cabinets Requirements, Minimum of 2.75 inches 7 cm