QuickSpecs
HP ProLiant BL25p Server Blade
Technical Specifications
Operating and
Performance Specifications for Power Distribution Devices
| Power Bus Box | Mini Bus Bar | Scalable Bus Bar |
Power | 1 | 1 | 2 |
Enclosures or facility DC |
|
|
|
feeds Supported |
|
|
|
(3U each) |
|
|
|
Server blade enclosures | 1 | 3 | 5 |
supported |
|
|
|
(6U each) |
|
|
|
Total rack height of | 9U | 21U | 36U |
supported enclosures |
|
|
|
Dimensions |
|
|
|
Height | 5.1 in (12.95 cm) | 19.45 in (49.40 cm) | 48.57 in (123.37 cm) |
Width | 3.6 in (9.14 cm) each | 19.74 in (50.14 cm) | 19.74 in (50.14 cm) |
Depth | 3.25 in (8.26 cm) | 2.2 in (5.59 cm) | 2.2 in (5.59 cm) |
Weight | 3.62 lb (1.64 kg) | 13.2 lb (5.9 kg) | 26 lb (11.79 kg) |
Rated Operating | |||
Voltage |
|
|
|
Max Total Power | 3000 W | 9000 W | 15000 W |
Supported |
|
|
|
Total Max Input Current | 69.44 A at | 208.32 A at | |
At Minimum Voltage |
|
| (equivalent of 175A per |
|
|
| feed) |
Total Max Input Current | 62.5 A at | 187.5 A at | 312.5 A at |
At Nominal Voltage |
|
| (equivalent of 175A per |
|
|
| feed) |
Max Current Per Power | 70A | 70A | 210A |
Feed |
|
|
|
Max Local Ambient | 149° F (65° C) | 149° F (65° C) | 149° F (65° C) |
Temperature |
|
|
|
NOTE: All systems support redundant A & B feeds. Scalable bus bar supports dual A and dual B feeds.
Operating and | Voltage | Nominal input voltage | |
Performance |
| Operating voltage range | |
Specifications for |
| ||
| Max Input voltage slew | 0.5V/uS | |
Facility DC |
| ||
| rate |
| |
|
|
| |
|
| Redundant feed voltages* | *A and B feeds must differ by no more than |
|
| (A & B) | 5VDC during steady state operation |
|
| Ripple/Noise | 480 mV PARD** |
|
| Overshoot | Must remain within regulation limits on all feeds |
|
|
| during startup or shutdown |
|
| Voltage transients | Must not exceed |
DA - 12160 North America — Version 7 — June 27, 2005 | Page 44 |