HP 275 manual Single-Phase Model Three-Phase Model Dimensions, Weights, Input Requirements

Models: 275

1 45
Download 45 pages 61.59 Kb
Page 43
Image 43

QuickSpecs

HP ProLiant BL25p Server Blade

Technical Specifications

Relative Humidity

Operating

20% to 80%

(non-condensing)

Non-operating

5% to 95%

 

Wet Bulb

Operating

82.4° F (28° C)

Temperature

Non-operating

101.7° F (38.7° C)

 

NOTE: Operating temperature has an altitude derating of 34° F/1° C per 1,000 ft/304.8 m. No direct sunlight. Upper operating limit is 10,000 ft/3,048 m or 70Kpa/10.1 psia. Upper non-operating limit is 30,000 ft/9,144 m or 30.3 KPa/4.4 psia. Storage maximum humidity of 95% is based on a maximum temperature of 113° F/45° C. Altitude maximum for storage is 70 KPa.

Operating and

Performance Specifications for Power Enclosures

 

 

Single-Phase Model

Three-Phase Model

Dimensions

Height

5.25 in (13.34 cm)

5.25 in (13.34 cm)

 

Width

27.15 in (68.96 cm)

27.15 in (68.96 cm)

 

Depth

17.60 in (44.7 cm)

17.60 in (44.7 cm)

Weights

No Hot-Plug

47.5 lb (21.55 kg)

47.5 lb (21.55 kg)

 

Power Supplies

 

 

 

All Hot-Plug

99.5 lb (45.13 kg)

125.5 lb (56.93 kg)

 

Power Supplies

 

 

Input Requirements

Rated input voltage

200 VAC to 240 VAC

200 VAC to 240 VAC

 

 

 

line to line

 

Rated input frequency

50 Hz to 60 Hz

50 Hz to 60 Hz

 

Rated input current

24A

24A per phase

 

per side

 

 

 

Rated input power

5760 W

9976 W

 

per side

 

 

 

Power cord

1 NEMA L6-30P per

1 NEMA L15-30 per

 

 

side

side

Output Voltage

Rated output voltage

-48.8 VDC to -54 VDC

-48.8 VDC to -54 VDC

Specifications

Rated output current

99A

170A

 

 

Rated output power

4298 W

8310 W

 

Nominal power

4158 W at 208 VAC

7202 W at 208 VAC

Ambient Temperature

Operating

50° to 95° F

50° to 95° F

Range (See NOTE)

 

(10° to 35° C)

(10° to 35° C)

 

Shipping

-22° to 140° F

-22° to 140° F

 

 

(-30° to 60° C)

(-30° to 60° C)

Relative humidity,

Operating

20% to 80%

20% to 80%

non-condensing

Non-operating

5% to 95%

5% to 95%

(See NOTE)

 

 

 

Wet Bulb

Operating

82.4° F (28° C)

82.4° F (28° C)

Temperature

Non-operating

101.7° F (38.7° C)

101.7° F (38.7° C)

 

NOTE: Operating temperature has an altitude derating of 34° F (1° C) per 1,000 ft (304.8 m). No direct sunlight. Upper operating limit is 10,000 ft (3,048 m) or 70Kpa/10.1 psia. Upper non-operating limit is 30,000 ft (9,144 m) or 30.3 KPa/4.4 psia. Storage maximum humidity of 95% is based on a maximum temperature of 113° F (45° C). Altitude maximum for storage is 70 KPa.

DA - 12160 North America — Version 7 — June 27, 2005

Page 43

Page 43
Image 43
HP 275 manual Single-Phase Model Three-Phase Model Dimensions, Weights, Input Requirements, Output Voltage, Specifications