HP BL30p Server Blades BL30p manual Standard Features Power System and Rack Information

Models: BL30p Server Blades BL30p

1 48
Download 48 pages 62.45 Kb
Page 14
Image 14

QuickSpecs

HP ProLiant BL30p Server Blade

Standard Features (Power System and Rack Information)

HP BladeSystem

NOTE: To determine power configuration, please refer to the HP BladeSystem p-Class Overview and

p-class Power System and

Planning Whitepaper and sizing utility at http://www.hp.com/products/servers/proliant-bl/p-class/info/.

Rack Information

 

 

 

HP BladeSystem p-Class

3U (5.25-inch), 19-inch wide, 29-inch deep (0.48-meter wide, 0.74-meter deep), dual input single

3U Power Enclosure

phase and three phase models available.

 

HP BladeSystem p-Class 3U power enclosure provides scalable rack-centralized, hot-plug power without

 

the need for PDUs.

 

Each 3 phase power enclosure houses six hot-plug power supplies

 

Each single-phase power enclosure holds four hot-plug power supplies

 

Please use the sizing utility to determine the power needed for each configuration

 

http://www.hp.com/go/bladesystem/powercalculator

 

NOTE: 3 phase power enclosure options highly recommended for HP ProLiant BL30p server blade

 

deployments.

 

Power enclosures and power supplies are not needed if using facility DC (-48V DC ± 10%). If using

 

facility DC, Facility DC Power Connection kit (240563-B21) is needed.

 

 

HP BladeSystem p-Class

1U (1.75-inch), 19-inch wide, 29-inch deep (0.48-meter wide, 0.74-meter deep), Multi-input single

1U Power Enclosure

phase or three phase operation.

 

HP BladeSystem p-Class 1U power enclosure provides external, hot-plug power. Each 1U power

 

enclosure houses up to six hot-plug power supplies to power up to one server blade enclosure, fully

 

populated with BL p-Class server blades and interconnects.

 

Please use the sizing utility to determine the power needed for each configuration

 

http://www.hp.com/go/bladesystem/powercalculator

 

Power enclosures and power supplies are not needed if using facility DC (-48V DC ± 10%). If using

 

facility DC, only Facility DC Power Connection kit part number (240563-B21) is needed.

 

 

HP BladeSystem p-Class Power Distribution (only required with 3U power enclosures)

In the HP BladeSystem p-Class infrastructure, redundant -48 VDC power (from the power enclosures or facility DC power) is carried from the power enclosures to the server blade enclosures through bus bars (for multiple enclosures) or power bus boxes (for a single enclosure). Hinges attach the HP BladeSystem bus bars to the rack rails and provide easy rear access to the blade enclosures and interconnects. Power is distributed through independent A- and B-sided bus bars.

Three power distribution solutions are available depending on the size of the intended deployment (see table).

 

Power Enclosures Supported

Server Blade Enclosures

Max. Rack Space Occupied

 

 

Supported

 

Scalable Bus Bar

1 or 2

up to 5

36U

Mini Bus Bar

1 or 2*

up to 3

24U

Power Bus Box

1

1

9U

 

NOTE*: Dual power input kit for mini bus bar option (364565-B21) required to support two power

 

enclosures.

 

 

 

NOTE: To support a full 42U rack of BL p-Class server blades, use two stacked pairs of mini bus bars.

DA - 11958 Worldwide — Version 19 — August 15, 2005