Power supplies installed in bay 2 in each of the 1U power enclosures should also be connected to a different phase on the PDU. Figure 8 illustrates how 1U power enclosures should be connected with four power supplies installed.
NOTE: The grayscale outlets on the PDU in Figure 8 indicate which phase the outlet is attached to. The wires are color coded to distinguish the connections to power supplies installed in bus A and bus B. Power supplies are numbered in reverse because the view is from the rear of the 1U power enclosure.
Figure 8. HP BladeSystem
6 | 5 | 4 | 3 | 2 | 1 |
Phase 1
Phase 2
Phase 3
6 | 5 | 4 | 3 | 2 | 1 |
Phase 1
Phase 2
Phase 3
14