75
Updating the Firmware |
|
In This Section |
|
Updating the Console Switch Firmware................................................................................. | |
Updating the Interface Adapter Firmware Simultaneously .................................................... | |
Updating the Interface Adapter Firmware Individually ......................................................... |
Updating the Console Switch Firmware
NOTE: The PC or laptop used to upgrade the firmware must be running
Microsoft® Windows NT® or greater.
1.Connect the serial download cable to the serial download connector on the PC (must be running Windows®) and to the serial download connector ("Components" on page 17) on the rear panel of the HP KVM Server Console Switch.
2.Go to the folder where the firmware files are saved and run the WUpDateHP.exe file.
NOTE: The three .bin files must be in the same folder as the
WUpDateHP.exe file.
3.Select which language to install and enter the serial port number of the server to which the HP KVM Server Console Switch is attached.
4.Click Load. The update process begins.
The update process has three
5.Click Done.