HP Performance Optimized Data Center (POD) 20cp manual HP POD 20c storage requirements

Models: Performance Optimized Data Center (POD) 20cp

1 37
Download 37 pages 24.34 Kb
Page 23
Image 23

Assembly equipment locations

Item

Description

 

 

1

Crane

2

Reach

3

Truck

4

Area clear for scissors lift and forklift

HP POD 20c lifting requirements

WARNING: The only approved method for lifting the HP POD 20c is the use of a spreader bar harness. Lifting an HP POD 20c in any other manner can cause damage to the HP POD 20c and void your warranty. The harness and lifting connections must be perpendicular to the lifting blocks.

HP POD 20c storage requirements

If the site is not ready for assembly and operation, determine a location for storage when creating the site plan.

CAUTION: The HP POD 20c must maintain 20% relative humidity to minimize condensation and oxidation within the HP POD 20c.

CAUTION: While being stored, the HP POD 20c must be kept in a level position even if stored on a trailer.

Changes in ambient temperatures can cause condensation in a non-operational HP POD 20c. If the HP POD 20c is placed in storage or is in non-operating mode for over 72 hours, HP recommends using one of the following methods to minimize condensation and oxidation within the HP POD 20c:

Desiccant unit

Desiccant material

Heater with a fan

Air conditioner with a heater strip

Consult with HP Services to determine the most effective method.

Site plan requirements and actions 23

Page 23
Image 23
HP Performance Optimized Data Center (POD) 20cp HP POD 20c storage requirements, Assembly equipment locations Description