Item

 

Description

Initial

 

 

 

 

2

 

Verify that the chilled water supply temperature meets the minimum POD chilled water supply

 

 

 

temperature of 12°C (55°F).

 

3

 

Verify that a sufficient chilled water flow rate is available.

 

4

 

If necessary, verify that the customer-required chilled water return temperatures can be

 

 

 

attained.

 

Power Requirements

 

 

 

 

Item

 

Description

Initial

 

 

 

 

1

 

Verify that the short circuit analysis, arc flash, and circuit breaker coordination studies are

 

 

 

complete. Verify power work is completed according to the approved conduit routing

 

 

 

drawings that show the exact routes, plan view, sections, and elevations.

 

2

 

Verify that temporary site power for installation and construction is planned and available, if

 

 

 

applicable.

 

3

 

Verify that adequate site power exists per the HP POD 20c requirements.

 

General

 

 

 

 

 

Item

 

Description

Initial

 

 

 

 

1

 

Verify the utility connection to the HP POD 20c and any required metering equipment.

 

2

 

Verify the third-party commissioning services that might be required by the owner.

 

3

 

Verify that the HP Project Team coordinates with other site construction activities.

 