Configuration setting (VAC)

Available nominal output voltage (VAC)

 

 

230

230

 

 

240

240

 

 

Output tolerance specifications

Source of power

Regulation

 

 

Utility power (nominal

-10% to +6% of nominal output voltage rating

range)

(within the guidelines of the Computer Business

 

Equipment Manufacturers Association)

 

 

Battery power

±5% of nominal output voltage rating

 

 

Output feature specifications

Feature

Specification

 

 

Online efficiency

94% nominal input voltage

 

 

Voltage wave shape

Sine wave; 5% THD with typical PFC load; 15-20% THD on battery

 

 

Surge suppression

High-energy 6500 A peak

 

 

Noise filtering

MOVs and line filter for normal and common mode use

 

 

Battery specifications

Feature

Specification

 

 

Type

12 V, 9 AH, sealed, maintenance-free, rechargeable, lead-acid battery.

 

 

Charging

Complete charge takes no more than 24 hours. After approximately 4 hours, the batteries

 

reach 90% charge at default nominal utility voltage and no load.

 

 

Battery runtime

Load, percent

Load, watts

Estimated battery runtime at 100% battery charge

 

 

 

20

100

45 minutes

 

 

 

50

250

15 minutes

 

 

 

80

400

6 minutes

 

 

 

100

500

4 minutes

 

 

 

Environmental specifications

Feature

Specification

 

 

Operating temperature

0°C to 40°C (32°F to 104°F)

 

 

Nonoperating temperature

-15°C to 50°C (5°F to 122°F)

 

 

Relative humidity

0% to 95%; noncondensing

 

 

Specifications 33