MA7200 PLUS Inverter 1 to 2 HP PID Fan and Pump Quick Start Manual

__________________________________________________________________

To further cover the PID Sleep function, the following is an example of the various parameter settings that could be used. In this example the system will have the following specifications:

-Max. Pump Motor Speed : 3600 RPM.

-Set Point: 150 PSI.

-Feedback Transducer Range: 0 – 200 PSI.

-Pump System Sleep Level: 2160RPM or 60% of max. speed set by

(P21-01=060.00).Sleep Level Delay Time: 10 sec. set by (P2-02=010.0 ).

-Pump System Wakeup Level: 100 PSI set by (P2-03=0100).Wakeup Time: 5 sec. set by (P2-04=005.0).

Referring to Step 9, set the engineering units to PSI (P1-01=02)and then the range to 200

(P1-02=0200).

On the following pages the keypad navigation sequence is shown in setting the PID parameters.

NOTE: The inverter must be in the Stop mode in order to turn on the sleep function.

________________________________________________________________ 17