MA7200 PLUS Inverter 1 to 2 HP PID Fan and Pump Quick Start Manual

__________________________________________________________________

Step 8– Select PID control (Sn-64), and Feedback input (Sn – 24) [4 – 20 mA or 0 – 10 Vdc]

Before selecting the parameter(s), ensure the inverter is in the STOP mode.

To activate PID control parameter (Sn-64)must be set to =1.

The Feedback Input parameter (Sn –24)is set to = 1 (AIN, 4-20 mA), as factory default. To select (VIN, 0-10 Vdc), (Sn-24)must be set to 0. (See Figs. 3a, 3b and 3c for feedback connections)

To set the parameter(s), follow the navigation procedure as shown next.

(Turn on PID control)

1 - Press the key

2 - Press the key twice

3 - Press the key until display shows

4 - Press the key

5 - Press the key

6 - Press the key to .

7 - Press the key to return to the main display.

Flashing

0

Flashing

1

2 Seconds

Flashing

1

________________________________________________________________ 9

TECO – Westinghouse Motor Company