MA7200 PLUS Inverter 1 to 2 HP PID Fan and Pump Quick Start Manual

__________________________________________________________________

Step 11 – Setting parameters acceleration (Bn-01) and deceleration (Bn-02) times

Acceleration and Deceleration times as well as the PID control [(P) Proportional Gain and/or the (I) Integral Time (see STEP 11) directly control the system dynamic response. The longer the acceleration and deceleration time, the slower the system response, and the shorter time, the faster the response. An excessive amount of time can result in sluggish system performance while too short of a time may result in system instability.

The starting values suggested by this guide normally result in good system performance for the majority of fan and pump applications. If the values need to be adjusted, caution should be exercised, and the changes should be in small increments to avoid system instability.

Parameters Bn-01(Acceleration) and Bn-02(Deceleration) are both set at the factory for 10.0 seconds. For fan and pump applications, the recommended starting values are 30 seconds. To change these parameters, follow the keypad navigation procedure as shown next.

To set parameter Bn-01 = 30.0 s

(Acceleration Time )

Keypad Steps

 

Resulting Display

1 - Press the

PRGM

key

 

 

 

An – 01 -

DRIVE

 

 

 

Freq. Cmd. 1

 

 

 

 

 

 

 

 

 

 

 

2 - Press the

DSPL

key

 

 

 

Bn-01

 

 

 

Acc. Time 1

 

 

 

 

 

 

Flashing

3 - Press the

4 - Press the

5 - Press the

EDIT

ENTER

RESET

EDIT

ENTER

key

 

 

 

 

 

 

Bn-01 = 0010.0

 

 

 

 

 

 

Acc. Time 1

 

 

 

 

 

 

 

key 3 times; then the

Key twice

 

 

Bn-01 = 0030.0

 

 

Acc. Time 1

 

 

 

 

 

 

 

key to save.

 

 

 

 

 

Entry Accepted

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Next set Bn-02 = 0030.0

 

 

 

Bn-01 = 0030.0

 

 

 

Acc. Time 1

 

 

 

 

 

 

 

Flashing

2Seconds

Flashing

________________________________________________________________ 15

TECO – Westinghouse Motor Company