LED and audible alarm troubleshooting

Condition

Power

On

Overloa

General

Audible alarm

Can

 

On LED

Battery

d LED

Alarm LED

 

alarm be

 

(green)

LED

(red)

(red)

 

silenced

 

 

(yellow)

 

 

 

("Silencin

 

 

 

 

 

 

g an

 

 

 

 

 

 

audible

 

 

 

 

 

 

alarm"

 

 

 

 

 

 

on page

 

 

 

 

 

 

24)?

 

 

 

 

 

 

 

UPS operating from

On

Off

Off

Off

No audible alarm

N/A

utility

 

 

 

 

 

 

 

 

 

 

 

 

 

Buck mode (high

On

Off

Off

Off

No audible alarm

N/A

input voltage)

 

 

 

 

 

 

 

 

 

 

 

 

 

Boost mode (low

On

Off

Off

Off

No audible alarm

N/A

input voltage)

 

 

 

 

 

 

 

 

 

 

 

 

 

Over temperature

On

On

Off

Flashing

On—Continuous

No

condition

 

 

 

 

 

 

 

 

 

 

 

 

 

Battery test failure

Off

On

Off

Flashing

On—Continuous

Yes

 

 

 

 

 

 

 

Fan failure

On

Off

Off

Flashing

On—Continuous

No

 

 

 

 

 

 

 

Output short circuit

On

On

On

Flashing

On—Continuous

No

 

 

 

 

 

 

 

Power up failure

Flashing

Flashing

Flashing

Flashing

On—3 beeps/10

No

from a DC start—

 

 

 

 

seconds

 

Low battery (no

 

 

 

 

 

 

utility power)

 

 

 

 

 

 

 

 

 

 

 

 

 

Low battery (no

Off

Flashing

Off

Off

On—2 second

No

utility power)

 

 

 

 

beep

 

 

 

 

 

 

 

 

Online—UPS power

On

Off

On

Off

On—1 second

No

capacity exceeded

 

 

 

 

beep

 

 

 

 

 

 

 

 

Overload timeout

Off

Off

On

Flashing

On—Continuous

No

 

 

 

 

 

 

 

On battery—Input

On

On

Off

Off

On—2 second

Yes

voltage is out of

 

 

 

 

beep

 

range

 

 

 

 

 

 

 

 

 

 

 

 

 

On battery—No

Off

On

Off

Off

On— 4 second

Yes

utility power

 

 

 

 

beep

 

 

 

 

 

 

 

 

On battery—Battery

Flashing

Off

Off

Flashing

On—Continuous

Yes

voltage condition

 

 

 

 

 

 

 

 

 

 

 

 

 

On battery—

Off

On

On

Off

On—1 second

No

Overload condition

 

 

 

 

beep

 

 

 

 

 

 

 

 

Troubleshooting 33