Feature

Specification

 

 

Charging

Advanced charging for faster recovery. Complete charge takes

 

no more than 24 hours. After approximately 4 hours, the

 

batteries reach 90% charge at default nominal utility voltage and

 

no load.

 

 

Battery runtime

Load, percent

Load, watts

Estimated battery runtime at 100% battery charge

 

 

 

20

200

58 minutes

 

 

 

50

500

17 minutes

 

 

 

80

800

8 minutes

 

 

 

100

1000

5 minutes

 

 

 

Environmental specifications

Feature

Specification

 

 

Operating temperature

0°C to 35°C (32°F to 95°F)

 

 

Nonoperating

-15°C to 55°C (5°F to 131°F)

temperature

 

 

 

Relative humidity

5% to 95%; noncondensing

 

 

Operating altitude

Up to 3,000 m (9,843 ft) above sea level

 

 

Nonoperating altitude

Up to 15,000 m (49,212 ft) above sea level

 

 

Audible noise

Less than 45 dBA

 

 

Serial communications port pin assignment

Specifications 38

Page 38
Image 38
HP UPS R1500 GENERATION 2 manual Battery runtime, Environmental specifications, Serial communications port pin assignment