SECTION IV – TROUBLESHOOTING
SOLAR WATER SYSTEM
Symptom | Probable Cause | Corrective Action / Remedy |
Gradual loss of heating | Tubes are fouled. | Clean tubes per Section III, annual |
capacity. |
| scheduled maintenance. |
| Excess silt in bottom of tank. | Drain and flush tank per Section III , |
|
| annual scheduled maintenance. |
Overheating. | Ruptured tube(s) in heating | Remove / replace heating coil. |
| coil. |
|
| Thermostat needs adjusting. | Adjust thermostat |
| Circulator not operating. | Repair or replace per separate O&M. |
Immediate loss of heating | Blockage in return line. | Clean blockage from return line. |
capacity. |
|
|
Excessive vibration. | High rate of flow beyond | Consult factory. |
| design conditions. |
|
| Under sized piping to the | |
| unit. | sized lines. |
Water hammer. | Undersized return lines. | |
|
| lines. |
| Insufficient slope on return | Increase slope on return lines. |
| lines causing backup. |
|
*Red symptom indicates that equipment should be shut down immediately and cause of malfunction corrected before unit is