GASBOY Series 70 & 1820
PUMP WIRING DIAGRAMS
115VAC Pumps Series 70 and 1820 (left) and Series 1820R (right)
230VAC Pumps Series 70 and 1820 (left) and Series 1820R (right)
NOTE FOR 230V MOTORS: Some motors may contain different wire colors than those shown. In this case, Hot is Black, Neutral is White and Aux AC Control is Brown.
1.All wiring and conduit runs must conform with all building/fire codes, all Federal, State, and Local codes, National Electrical Code, (NFPA 70), NFPA 30, Automotive and Marine Service Station Code (NFPA 30A), and NFPA 395 codes and regulations.
2.For the Series 70 and Series 1820 rounded cabinet models, make the field wire connections in the motor junction box. The 1820R models with the squared cabinet come with the wires already extended through the end of a
3.The Aux AC Control Lead wire is shipped capped from the factory. When used, it connects to a solenoid valve or fuel management system. Do not connect this wire without first checking the ON voltage of this line to ascertain compatibility with the equipment being connected.
4.Pulser wiring must be 18AWG and installed in metal conduit separate from all AC wiring. It cannot share a common junction box, wiring trough or conduit with any AC wiring.