Diagnostic Utility

The uninterruptible power supply has a diagnostic feature that displays the utility voltage.

Voltage

Plug the uninterruptible power supply into the utility power outlet.

 

The uninterruptible power supply starts a self-test as part of this procedure. The

 

self-test does not affect the voltage display.

 

Press and hold the

button to view the utility voltage bar graph display. After a few

 

seconds, this five-LED Battery Charge

display on the right of the front panel will

 

show the utility input voltage.

 

 

Refer to the figure at left for the voltage reading, corresponding to the configured nominal

 

output voltage.

 

 

 

The display indicates the voltage is between the displayed value on the list and the next

 

higher value.

 

 

 

If three LEDs are illuminated, the utility voltage is within the normal range. If no LEDs

 

are illuminated and the uninterruptible power supply is plugged into a properly function-

 

ing utility power outlet, the line voltage is extremely low. If all five LEDs are illuminated,

 

the line voltage is extremely high and should be checked by an electrician.

 

 

 

 

On Battery Operation

The IBM uninterruptible power supply switches to battery operation automatically if the utility power fails. While running on battery, an alarm beeps four times every 30 seconds.

Press the button to silence this uninterruptible power supply alarm. If the utility power does not return, the uninterruptible power supply continues to supply power to the connected equipment until the battery is fully discharged.

If you are not using PowerChute, shut down the operating system and turn off the computer before the uninterruptible power supply fully discharges the battery.

Determining On Battery Runtime

The uninterruptible power supply battery charges when connected to utility power. The battery charges to 90% capacity during the first three hours of normal operation. Do not expect full battery run capability during the initial charge period.

Battery Runtime Table

This chart shows the typical on-battery runtime in minutes.

Load (VA)

Load

750VA

1000VA

1500VA

 

(watts)

 

 

 

50

30

105

224

269

100

60

57

127

157

200

122

28

64

80

300

184

18

41

51

400

247

13

29

37

500

311

9.7

23

28

600

377

7.7

18

22

700

447

6.4

15

18

750

500

5.0

13.5

16.5

800

511

12

15

900

579

11

13

1000

700

8

11

1200

790

9.0

1400

936

7.4

1440

1050

6.7

1500

1050

6.7

8