IBM UPS1500TLV, UPS750TLV, UPS1000TLV, UPS1000THV, UPS750THV manual Replace Battery LED is Illuminated

Models: UPS1000TLV UPS1500THV UPS750THV UPS1000THV UPS1500TLV UPS750TLV

1 68
Download 68 pages 31.46 Kb
Page 19
Image 19

PROBLEM AND/OR POSSIBLE

 

SOLUTION

CAUSE

 

 

THE REPLACE BATTERY LED IS ILLUMINATED

Replace battery LED flashes

 

Check that the battery connectors are fully engaged.

and short beep is emitted every

 

 

two seconds to indicate the

 

 

battery is disconnected.

 

 

 

 

 

Weak battery.

 

Allow the battery to recharge for 24 hours. Then, perform a self-test. If the

 

 

problem persists after recharging, replace the battery.

 

 

 

Failure of a battery self-test.

 

The uninterruptible power supply emits short beeps for one minute and the

 

 

replace battery LED illuminates. The uninterruptible power supply repeats

 

 

the alarm every five hours. Perform the self-test procedure after the battery

 

 

has charged for 24 hours to confirm the replace battery condition. The

 

 

alarm stops and the LED clears if the battery passes the self-test.

 

 

THE SITE WIRING FAULT LED ON THE REAR PANEL IS ILLUMINATED (750TLV, 1000TLV & 1500TLV

MODELS ONLY)

 

 

The uninterruptible power sup-

 

Wiring faults detected include missing ground, hot-neutral polarity reversal,

ply is plugged into an improp-

 

and overloaded neutral circuit.

erly wired utility power outlet.

 

Contact a qualified electrician to correct the building wiring.

 

 

 

 

THE INPUT CIRCUIT BREAKER HAS TRIPPED

The plunger on the circuit

 

Reduce the load on the uninterruptible power supply by unplugging equip-

breaker pops out.

 

ment. Press in the plunger on the circuit breaker.

 

 

THE AVR BOOST OR TRIM LEDS ARE ILLUMINATED

Your system is experiencing

 

Have qualified service personnel check your facility for electrical prob-

excessive periods of low or

 

lems. If the problem continues, contact the utility company for further as-

high voltage.

 

sistance.

 

 

UNINTERRUPTIBLE POWER SUPPLY OPERATES ON BATTERY ALTHOUGH NORMAL LINE VOLTAGE

EXISTS

 

 

The uninterruptible power

 

To reduce the load on the uninterruptible power supply, unplug equipment

supply input circuit breaker

 

and press in the plunger on the circuit breaker.

tripped.

 

 

 

 

 

Very high, low, or distorted

 

Move the uninterruptible power supply to a different outlet on a different

line voltage.

 

circuit, as inexpensive fuel powered generators may distort the voltage. Test

 

 

the input voltage with the utility voltage display (see Operation). If accept-

 

 

able to the connected equipment, reduce the uninterruptible power supply

 

 

sensitivity.

 

 

BATTERY CHARGE AND BATTERY LOAD LEDS FLASH SIMULTANEOUSLY

The uninterruptible power

 

Check that the room temperature is within the specified limits for operation.

supply has shutdown. The

 

Check that the uninterruptible power supply is properly installed, allowing

internal temperature of the

 

 

for adequate ventilation.

uninterruptible power supply

 

 

 

has exceeded the allowable

 

Allow the uninterruptible power supply to cool down. Restart the uninter-

threshold for safe operation.

 

ruptible power supply. If the problem continues, contact IBM.

 

 

 